Study of a novel silica gel–water adsorption chiller. Part II. Experimental study |
| |
Authors: | DC Wang JY Wu ZZ Xia H Zhai RZ Wang WD Dou |
| |
Affiliation: | aInstitute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai 200030, China;bJiangsu Shuangliang Air Conditioning Equipment Co., Ltd, Jiangsu 214444, China |
| |
Abstract: | The prototype of a novel silica gel–water adsorption chiller is built and its performance is tested in detail. The experimental results show that the refrigerating capacity (RC) and COP of the chiller are 7.15 and 0.38 kW, respectively, when the hot water temperature is 84.8 °C, the cooling water temperature is 30.6 °C, and the chilled water outlet temperature is 11.7 °C. The RC will reach 6 kW under the condition of 65 °C hot water temperature, 30.5 °C cooling water temperature and 17.6 °C chilled water temperature. The results confirm that this kind of adsorption chiller is an effective refrigerating machine though its performance is not as fine as the prediction results. Also it is well effectively driven by a low-grade heat source. Therefore, its applications to the low-grade heat source are much attractive. |
| |
Keywords: | Experiment Adsorption system Water Silica gel Performance COPMots clé s: Expé rimentation Systè me à adsorption Eau Gel de silice Performance COP |