首页 | 官方网站   微博 | 高级检索  
     

基于参数识别的并联电抗器保护
引用本文:索南加乐,田宏强,谢雯洁,张鹏,杜岩平,周德生.基于参数识别的并联电抗器保护[J].电力系统自动化,2008,32(22):47-51.
作者姓名:索南加乐  田宏强  谢雯洁  张鹏  杜岩平  周德生
作者单位:西安交通大学电气工程学院,陕西省西安市 710049
摘    要:针对目前并联电抗器保护性能的不足,提出了基于参数识别的并联电抗器保护新原理,即通过求取参数 L和R,利用并联电抗器内、外部故障时的参数方向关系和阻抗幅值关系来判别故障方向。由于参数 L,R和系统频率无关,且该方法为解微分方程法,因此该方法从原理上不受系统频率变化、振荡等影响,且受非周期分量的影响相当小。动模实验验证表明,该方法能克服传统电抗器保护中存在的不足,尤其是能有效地解决在轻微匝间故障时存在的动作死区问题,用该方法实现的保护简单、可靠、动作迅速。

关 键 词:并联电抗器保护  参数识别    R-L模型  最小二乘法
收稿时间:1/15/2008 3:07:17 PM
修稿时间:2008/11/11 0:00:00

Shunt Reactor Protection Based on the Parameter Identification
SUONAN Jiale,TIAN Hongqiang,XIE Wenjie,ZHANG Peng,DU Yanping,ZHOU Desheng.Shunt Reactor Protection Based on the Parameter Identification[J].Automation of Electric Power Systems,2008,32(22):47-51.
Authors:SUONAN Jiale  TIAN Hongqiang  XIE Wenjie  ZHANG Peng  DU Yanping  ZHOU Desheng
Abstract:A new shunt reactor protection principle is proposed based on the parameter identification method. The values of resistance and inductance are calculated firstly. Then according to the relationships between the parameter directions and the magnitudes of impedances in the internal and external faults respectively, the direction of faults are determined. Because the values of resistance and inductance are not related to the system frequency, and the method is of differential equation, it is not affected by the system frequency change or oscillations,and the non-periodical components have little influence on the results. Dynamic simulation results demonstrate that the method can overcome the shortcomings of the traditional reactor protection, especially the problem of operating dead zone when internal turn-to-turn fault occurs. The method features simplicity, high reliability and fast reaction speed.
Keywords:shunt reactor protection  parameter identification  R-L model  least square method
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23