首页 | 官方网站   微博 | 高级检索  
     

蓄能机组轴线问题及机组运行摆度偏高分析处理
引用本文:王志刚 刘建伟. 蓄能机组轴线问题及机组运行摆度偏高分析处理[J]. 水电站机电技术, 2003, 26(3): 52-55
作者姓名:王志刚 刘建伟
作者单位:十三陵蓄能电厂,十三陵蓄能电厂 北京昌平 102200,北京昌平 102200
摘    要:十三陵蓄能电厂针对机组运行中水导摆度过大的问题,特别是2号机组在安装期间进行过加垫调整轴线,对全厂4台机组的轴线进行了彻底检查。本文通过对2号机组的轴线调整阐述了可逆式、高转速、高水头蓄能机组的轴线调整,从各方面分析了影响机组运行摆度的可能原因。

关 键 词:蓄能机组  轴线调整  导轴承间隙  十三陵蓄能电厂

Analysis and treatment of abnormal axis and throw of a pumped storage unit
Wang Zhigang,Liu Jianwei. Analysis and treatment of abnormal axis and throw of a pumped storage unit[J]. , 2003, 26(3): 52-55
Authors:Wang Zhigang  Liu Jianwei
Abstract:In order to solve the problem of over-throw of units in Shisanling Pumped Storage Plant,the axes all of 4 units were inspected. The axis of No. 2 Unit was adjusted by padding during installation. This paper discusses the axis trimming of a reversible,high-speed,high-head storage unit: and analyzes the causes of affecting the throw.
Keywords:pumped storage unit  axis trimming  guide bearing gap  Shisanling Pumped Storage Plant