首页 | 官方网站   微博 | 高级检索  
     


Mitigation of third‐harmonic voltage for three‐phase four‐wire distribution system based on a series active filter for neutral conductor
Authors:Keiji Wada  Shigenori Inoue  Toshihisa Shimizu
Abstract:This paper proposes a series active filter for mitigation of the third‐harmonic voltage in a three‐phase four‐wire power distribution system in a building. The active filter which consists of a single‐phase inverter can suppress the harmonic voltage of the system. The active filter is characterized by acting not only as a capacitor but also as a resistor for the third‐harmonic components. A Hilbert transformer is applied to the controller of the active filter in order to realize accurate third‐harmonic detection on a single‐phase active filter. Measurement results of harmonic distortion of source voltage in a building is also shown in this paper. It is clarified in a simulation and experiment that the active filter can suppress the third‐harmonic voltage without increasing neutral conductor current. © 2004 Wiley Periodicals, Inc. Electr Eng Jpn, 150(1): 62–70, 2005; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.10379
Keywords:third‐harmonic voltage  low‐voltage distribution system  three‐phase four‐wire pattern  series active filter