基于人工污秽试验的750 kV耐张瓷绝缘子紫外检测技术
引用本文:蔡晶,张楠,马众,彭敏,尚晓光,贾志东,王林军.基于人工污秽试验的750 kV耐张瓷绝缘子紫外检测技术[J].中国电力,2016,49(9):23-29.
作者姓名:蔡晶  张楠  马众  彭敏  尚晓光  贾志东  王林军
作者单位:1. 国网新疆电力公司检修公司,新疆 乌鲁木齐 830002;
2. 清华大学 深圳研究生院,广东 深圳 518055
摘    要:750 kV 输电线路的运行过程中需要对绝缘子进行及时有效的检测,紫外检测是一种快速高效的绝缘子放电检测技术,如何将这种方法应用到750 kV绝缘子检测中尤为重要。通过对750 kV瓷绝缘子进行人工污秽试验的紫外检测结果进行研究,提出了紫外光子数相对波动性以及帧光斑面积均值这2个评估绝缘子放电严重程度的特征量,发现2个特征量均可以有效地评估绝缘子放电严重程度。其结论对紫外检测技术在750 kV绝缘子检测中的应用具有重要意义。

关 键 词:紫外检测  紫外光子数  光斑面积  放电严重程度  
收稿时间:2016-01-08

Ultraviolet Detection Technology of 750 kV Resistant to Porcelain Insulator Based on Artificial Pollution Test
CAI Jing,ZHANG Nan,MA Zhong,PENG Min,SHANG Xiaoguang,JIA Zhidong,WANG Linjun.Ultraviolet Detection Technology of 750 kV Resistant to Porcelain Insulator Based on Artificial Pollution Test[J].Electric Power,2016,49(9):23-29.
Authors:CAI Jing  ZHANG Nan  MA Zhong  PENG Min  SHANG Xiaoguang  JIA Zhidong  WANG Linjun
Affiliation:1. State Grid Xinjiang Electric Power Company Maintenance Company, Urumqi 830002, China;
2. Graduate School at Shenzhen, Tsinghua University, Shenzhen 518055, China
Abstract:Timely and effective testing of insulators is essential to safe operation of 750 kV transmission line. As a fast and efficient method to detect insulator discharge, ultraviolet detection technique is very important in insulator detection. Ultraviolet detection result of the 750 kV Porcelain Insulator by using artificial pollution test is analyzed first. Two characteristic quantity indexes, fluctuation range of photon number and mean value of spot area, are proposed to evaluate discharge severity. Both indexes can effectively evaluate degree of insulator discharge. The testing results are of great significance to application of UV detection technology in 750 kV insulator testing.
Keywords:UV detection  UV photon number  spot area  discharge severity  