首页 | 官方网站   微博 | 高级检索  
     

基于熵权法的华中500 kV高压输电线路雷击跳闸情况分析
引用本文:柳双,杜志叶,王俊,岳国华,顾德文,汪旸,甘艳.基于熵权法的华中500 kV高压输电线路雷击跳闸情况分析[J].现代电力,2021,38(3):332-338.
作者姓名:柳双  杜志叶  王俊  岳国华  顾德文  汪旸  甘艳
作者单位:1.武汉大学电气与自动化学院,湖北省武汉市 430072
摘    要:鉴于近年来极端天气不断出现,以往的雷电统计规律和趋势与当前的实际情况之间有较大的差异,对线路防雷评估带来较大的误差.通过对华中区域数十条500 kV线路走廊10 km范围内近年的落雷数据进行分析,从含后续回击的主放电、不含后续回击的主放电以及后续回击3种类型分析该区域雷电放电的相关规律,发现含后续回击的主放电次数最少....

关 键 词:主放电  后续回击  雷电流极性  熵权法  雷击跳闸
收稿时间:2020-11-29

Entropy Weight Method Based Analysis on Lightning Trip in Central China 500 kV Transmission Lines
Affiliation:1.School of Electrical and Automation, Wuhan University, Wuhan 430072, Hubei Province, China2.Central China Branch of State Grid Corporation, Wuhan 430077, Hubei Province, China
Abstract:Due to constantly appearing of extreme weather in recent years, it leads to a big difference between the previous statistical law and trend of lightning and the current actual situation, and it brings obvious error in to the lightning protection evaluation of transmission lines. By means of analyzing the ground lightning data within the scope of 10 km width of dozens of 500 kV transmission line corridors in Central China, the relevant law of thunder discharges in these regions, which were divided into three types, i.e., the main discharge containing subsequent return stroke, the main discharge not containing subsequent return stroke and subsequent return stroke, was analyzed, and it was discovered that the times of the main discharge containing subsequent return stroke was the least. It was discovered also by analyzing the ground lightning with different polarities that the proportion of negative polarity discharge obviously varied with statistical patterns of discharge types, and in the total amount of the positive polarity discharge the proportion of the main discharge not containing subsequent return stroke was 79.33%. On the basis of above-mentioned analysis, the entropy weight method, by which the influences of the parameters of both main discharge and the subsequent return stroke on transmission line trip could be considered, was proposed. The weighted calculation results of practical transmission line show that the lightning trip of practical transmission lines is mainly caused by main discharge containing subsequent return stroke as well as the subsequent return stroke, thus, the proposed entropy weight method turns out to be true.
Keywords:
本文献已被 CNKI 等数据库收录!
点击此处可从《现代电力》浏览原始摘要信息
点击此处可从《现代电力》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号