首页 | 官方网站   微博 | 高级检索  
     

双母双分段母线保护配置及分段开关失灵改造
引用本文:汤弋,冯凝,李煜磊.双母双分段母线保护配置及分段开关失灵改造[J].华中电力,2011,24(4):72-75.
作者姓名:汤弋  冯凝  李煜磊
作者单位:湖北省超高压输变电公司,湖北武汉,430050
摘    要:介绍了光谷变电站220kV双母双分段母线保护配置方式,分析了常规分段断路器启动失灵保护二次回路的缺点,提出了新的光谷变电站分段断路器失灵二次回路改造设计.并对BP-2B母线保护在分段单元刀闸断线接地故障时无法正确动作,提出了解复压闭锁改造设计.

关 键 词:双母双分段  分段开关失灵  复合电压闭锁

Busbar Protection Configuration and Subsection Switch Malfunction Modification for 4-sections Busbar
TANG Yi,FENG Ning,LI Yu-lei.Busbar Protection Configuration and Subsection Switch Malfunction Modification for 4-sections Busbar[J].Central China Electric Power,2011,24(4):72-75.
Authors:TANG Yi  FENG Ning  LI Yu-lei
Affiliation:HuBei EHV Transmission and Substation Company,Hubei EHV Transmission and Substation Company,Hubei EHV Transmission and Substation Company
Abstract:This article introduced the deployment of 4-section busbar protection for 220 kV lines in Guanggu transformer substation.The defects of normal subsection switch start-up malfunction protection in secondary circuit was analyzed,and a reform design on the secondary circuit for subsection switch malfunction protection in Guanggu transformer substation was proposed.The study puts forward a reform design of removing compound voltage blockout which can help solve the problem that the BP-2B busbar protection can't...
Keywords:4-sections busbar  subsection switch malfunction  compound voltage protection blockout  
本文献已被 CNKI 维普 万方数据 等数据库收录!
点击此处可从《华中电力》浏览原始摘要信息
点击此处可从《华中电力》下载全文