首页 | 官方网站   微博 | 高级检索  
     

DME或R600a与角鲨烷为工质对的吸收式制冷循环性能分析
引用本文:贾秀璨,罗勇,王晓坡.DME或R600a与角鲨烷为工质对的吸收式制冷循环性能分析[J].制冷学报,2022,43(2):62-69.
作者姓名:贾秀璨  罗勇  王晓坡
作者单位:西安交通大学能源与动力工程学院 热流科学与工程教育部重点实验室
基金项目:国家自然科学基金(51936009)
摘    要:本文分析了R600a/角鲨烷和DME/角鲨烷工质对在单效和压缩辅助吸收式制冷循环中的热力学性能.利用NRTL模型关联了两种工质对的汽液相平衡数据,分析了发生温度、蒸发温度和压缩机压比对循环性能系数(COP)、 效率和循环倍率的影响.结果表明:R600a工质对的性能更优.相比于单效循环,压缩辅助循环性能明显更高.在蒸发温...

关 键 词:制冷剂  润滑油  吸收式制冷  性能分析
收稿时间:2021/9/1 0:00:00
修稿时间:2021/10/14 0:00:00

Performance Analysis of Absorption Refrigeration Cycles Using DME or R600a and Squalane as Working Pair
Jia Xiucan,Luo Yong,Wang Xiaopo.Performance Analysis of Absorption Refrigeration Cycles Using DME or R600a and Squalane as Working Pair[J].Journal of Refrigeration,2022,43(2):62-69.
Authors:Jia Xiucan  Luo Yong  Wang Xiaopo
Abstract:The thermodynamic performance of R600a/squalane and DME/squalane working pairs in single-effect and compression-assisted absorption refrigeration systems was analyzed in this study. The vapor-liquid equilibrium data were correlated using the NRTL model. The effects of the generation temperature, evaporation temperature, and compressor pressure ratio on the COP, exergy efficiency, and circulation ratio were analyzed. The results show that the R600a/squalane working pair performed better. The performance of the compression-assisted cycle was significantly better than that of the single-effect cycle. At an evaporation temperature of 278.15 K, peaks occur in the COP and exergy efficiency curves for single-effect and compression-assisted cycles with the increase in evaporation temperature. At a generation temperature of 363.15 K, the COP of the two working pairs increases monotonously with the increase in evaporation temperature, and the exergy efficiency curves exhibit peaks. With increasing generation and evaporation temperatures, the maximum COP and exergy efficiency values for the R600a and DME working pairs in the two cycles were 0.675 and 0.655, respectively. The performance of the DME working pair increased with an increase in the compression ratio, whereas that of the R600a working pair peaked at a ratio of 1.5. The circulation ratio decreased as the generation temperature, evaporation temperature, and pressure ratio increased.
Keywords:refrigerant  lubricant oil  absorption refrigeration  thermodynamic performance