首页 | 官方网站   微博 | 高级检索  
     

溴化锂冷冻机组故障分析及处理
引用本文:王英俊. 溴化锂冷冻机组故障分析及处理[J]. 深冷技术, 2010, 0(3): 60-62
作者姓名:王英俊
作者单位:中国石油大庆石化公司水气厂,黑龙江省大庆市龙凤区卧里屯163714
摘    要:因为泄漏,溴化锂冷冻机组制冷能力严重下降。通过故障原因分析和实际监测,准确地判断出具体的泄漏部位和泄漏量。根据实际情况,用冬季温度较低的生活用水代替空分设备所需的冷却水,不仅为冷冻机组的检修留出足够的时间,而且为空分设备平稳生产提供了保障。

关 键 词:空气预冷系统  溴化锂冷冻机组  泄漏

Analysis and treatment of trouble of lithium bromide chiller set
Wang Yingjun. Analysis and treatment of trouble of lithium bromide chiller set[J]. Cryogenic Technology, 2010, 0(3): 60-62
Authors:Wang Yingjun
Affiliation:Wang Yingjun (Water & Gas Plant, Daqing Petrochemical Company, China National Petroleum Corporation, Wolitun , Longfeng District, Daqing 163714 , Heilongjiang, P. R. China)
Abstract:The refrigerating capacity of lithium bromide chiller set seriously drops due to leakage. The leaking location and the leakage volume are corrcctly judged through analysis of the trouble cause and the actual monitor. In winter, substitution of relative low-temperature domestic water . for the cooling water required for the air separation plant as per actual conditions provides sufficient time for repair of the chiller set and ensures steady production of air separation plant.
Keywords:Air pre-cooling system  Lithium bromide chiller set  Leakage