Effect of reliability of grounding of the shaft of a turboset on the operation of devices for control and protection of exciting circuits |
| |
Authors: | V K Voronin S A Evdokimov A I Leviush A L Trofimov |
| |
Affiliation: | (1) Cogeneration Plant “TéTs-22”, Russia;(2) Electric Power Research Institute (VNIIé), Russia;(3) Cogeneration Plant “TéTs-25”, Russia |
| |
Abstract: | Disturbance of the grounding of the shaft of a turboset or its absence for technical reasons can result in failure, misoperation,
limitation of the operating zone, errors or limitation of the sensitivity of devices for control and protection of exciting
circuits from single-point leakage, and electroerosion of elements of the turboset structure. Measures for increasing the
reliability of the grounding of the shaft are discussed.
__________
Translated from élektricheskie Stantsii, No. 3, March 2006, pp. 61–66. |
| |
Keywords: | turboset rotor exciting winding setting grounding and relay brushes insulation resistance ground loop |