单电源多级串供型输电线路距离保护误动原因分析及改进
引用本文:王宏宇,李永丽,张云柯,王伟康,曾治安,曹磊. 单电源多级串供型输电线路距离保护误动原因分析及改进[J]. 电力自动化设备, 2021, 41(2): 179-185. DOI: 10.16081/j.epae.202011023
作者姓名:王宏宇  李永丽  张云柯  王伟康  曾治安  曹磊
作者单位:天津大学 智能电网教育部重点实验室,天津 300072;天津大学 智能电网教育部重点实验室,天津 300072;天津大学 智能电网教育部重点实验室,天津 300072;天津大学 智能电网教育部重点实验室,天津 300072;国网重庆市电力公司,重庆 400011;国网河北省电力有限公司,河北 石家庄 050021
基金项目:国家电网有限公司总部科技项目(适应灵活可控源荷接入的新型城市电网继电保护关键技术研究及应用)
摘    要:结合一起单电源多级串供型输电线路距离保护误动的事例,详细探讨了保护误动的原因,分析指出:输电线路在保护安装处近区发生区外单相接地故障时,由于分布电容的影响,判断故障方向的负序方向元件将落入正向区内,引起保护误动.为解决上述问题,在传统负序方向元件判据的基础上提出了一种基于正序电流和负序电流之间相位关系的故障方向判据,并...

关 键 词:单电源  距离保护  继电保护  多级串供  分布电容  负序方向元件

Analysis and improvement of mal-operation in distance protection of multi-stage series transmission line with single power source
WANG Hongyu,LI Yongli,ZHANG Yunke,WANG Weikang,ZENG Zhian,CAO Lei. Analysis and improvement of mal-operation in distance protection of multi-stage series transmission line with single power source[J]. Electric Power Automation Equipment, 2021, 41(2): 179-185. DOI: 10.16081/j.epae.202011023
Authors:WANG Hongyu  LI Yongli  ZHANG Yunke  WANG Weikang  ZENG Zhian  CAO Lei
Affiliation:Key Laboratory of Smart Grid of Ministry of Education, Tianjin University, Tianjin 300072, China;State Grid Chongqing Electric Power Company, Chongqing 400011, China; State Grid Hebei Electric Power Co.,Ltd.,Shijiazhuang 050021, China
Abstract:Based on a case of mal-operation in distance protection of multi-stage series transmission line with single power source, the cause of mal-operation of protection are discussed in detail, which points out: when the external single-phase grounding fault near protection installation location of the transmission line, due to the influence of distributed capacitance, the negative-sequence direction component judging the fault direction will fall into the forward zone, causing the mal-operation of protection. In order to solve the above problems, a fault direction criterion based on the phase relation between positive-sequence current and negative-sequence current is proposed based on the traditional criterion of negative-sequence direction component, and the action interval of positive direction is given. The PSCAD/EMTDC simulation verifies that the proposed direction criterion is not affected by the transition resistance, and solves the problem of mal-operation of the distance protection when the external fault occurs near protection installation location.
Keywords:single power source   distance protection   relay protection   multi-stage collusion   distributed capacitance   negative-sequence direction component