SFZ9-CY-20000/220型变压器运行中油位降低的分析处理
引用本文:李宪栋,石月春. SFZ9-CY-20000/220型变压器运行中油位降低的分析处理[J]. 高压电器, 2010, 46(2)
作者姓名:李宪栋  石月春
作者单位:小浪底水力发电厂,河南,济源,454681;小浪底水力发电厂,河南,济源,454681
摘    要:为找到SFZ9-CY-20000/220型变压器运行中油位突然降低的原因,结合变压器油位监测系统原理进行了分析,并计算了变压器油体积随温度变化的情况,在变压器停运时进行了油位的确认和处理,认为吸湿器堵塞是造成变压器油位突然大范围降低的原因。

关 键 词:变压器  油位  降低  吸湿器

Analysis and Disposal of Oil Level Descending in SFZ9-CY-20000/220 Transformer During Operation
LI Xian-dong,SHI Yue-chun. Analysis and Disposal of Oil Level Descending in SFZ9-CY-20000/220 Transformer During Operation[J]. High Voltage Apparatus, 2010, 46(2)
Authors:LI Xian-dong  SHI Yue-chun
Affiliation:Xiaolangdi Hydropower Plant;Jiyuan 454681;China
Abstract:The cause of a sudden oil level descending in SFZ9-CY-20000/220 transformer during operation is analyzed according to the principle of transformer oil level detection.The change of oil volume with temperature is calculated,and the oil level is measured after the transformer stops operation.The conclusion is that the transformer oil level descending is induced by moisture absorber jam.
Keywords:transformer  oil level  descending  moisture absorber  