首页 | 官方网站   微博 | 高级检索  
     

电炉变压器的保护定值计算
引用本文:闻登沈,陈丽娟.电炉变压器的保护定值计算[J].黑龙江冶金,2011(3):50-51.
作者姓名:闻登沈  陈丽娟
作者单位:北满特殊钢有限责任公司;
摘    要:电炉冶炼熔化期电极及炉料或电极周围的炉料塌落而使电极二相或三相短路。电炉变压器在熔化期点弧及塌料时经常处于连续短路状态,这种工作短路是不可避免的,是正常现象。所以电炉变压器必须满足这一要求,但又必须采取措施,使工作短路电流的倍数和持续时间不超过规定值。根据冶炼工艺的要求和电炉电气设备标准规定,工作短路电流要小于3~3.5倍电炉变压器额定电流,持续时间小于6s,短路速断电流小于4—6倍电炉变压器的额定电流,持续时间0s。

关 键 词:变压器  继电保护  电炉

Arc Furnace Transformer Protection Setting Value Calculation
Authors:Wen Dengshen  Cheng Lijuan
Affiliation:Wen Dengshen,Cheng Lijuan(Dongbei Special Steel Group Beiman Special Steel Co.,Ltd.,Qiqihaer Heilongjiang 161041 China)
Abstract:Two phase or three-phase short-circuit took place often during electric smelting period around electrodes because of burden collapsing.The condition of short-circuit continuous short-circuit is inevitable and normal.So the arc furnace transformer is supposed to meet the requirement,and must adopt measures to make times of short-circuit current ratio in proper range.According to requirements of electric smelting process and electrical equipment standard,working short-circuit current is less than 3 ~ 3.5 time...
Keywords:Transformer  Relay protection  EF  
本文献已被 CNKI 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号