首页 | 官方网站   微博 | 高级检索  
     


Microbiology, chemistry and biofilm development in a pilot drinking water distribution system with copper and plastic pipes
Authors:Lehtola Markku J  Miettinen Ilkka T  Keinänen Minna M  Kekki Tomi K  Laine Olli  Hirvonen Arja  Vartiainen Terttu  Martikainen Pertti J
Affiliation:Laboratory of Environmental Microbiology, National Public Health Institute, P.O. Box 95, FIN-70701 Kuopio, Finland. markku.lehtola@ktl.fi
Abstract:We studied the changes in water quality and formation of biofilms occurring in a pilot-scale water distribution system with two generally used pipe materials: copper and plastic (polyethylene, PE). The formation of biofilms with time was analysed as the number of total bacteria, heterotrophic plate counts and the concentration of ATP in biofilms. At the end of the experiment (after 308 days), microbial community structure, viable biomass and gram-negative bacterial biomass were analysed via lipid biomarkers (phospholipid fatty acids and lipopolysaccharide 3-hydroxy fatty acids), and the numbers of virus-like particles and total bacteria were enumerated by SYBR Green I staining. The formation of biofilm was slower in copper pipes than in the PE pipes, but after 200 days there was no difference in microbial numbers between the pipe materials. Copper ion led to lower microbial numbers in water during the first 200 days, but thereafter there were no differences between the two pipe materials. The number of virus-like particles was lower in biofilms and in outlet water from the copper pipes than PE pipes. Pipe material influenced also the microbial and gram-negative bacterial community structure in biofilms and water.
Keywords:Drinking water  Biofilm  Microbes  Plastic  Copper
本文献已被 ScienceDirect PubMed 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号