首页 | 官方网站   微博 | 高级检索  
     


Near field coupling to shielded cable due to switching operation in substation
Authors:Lei QI  Xiang CUI
Affiliation:(1) Beijing Key Laboratory of High Voltage and EMC, North China Electric Power University, Beijing, 102206, China
Abstract:It is vital to study the electromagnetic coupling to shielded cable for improving electromagnetic antiinterference ability of secondary equipment in a substation. As a hybrid of method of moment (MoM) and transmission line method, a frequency domain model is put forward to study the near field coupling to shielded cable due to the switching operation in substation. Compared with the results of EMTP, the proposed method has been proven correct. Furthermore, this method overcomes the disadvantage of EMTP, which is only applicable for transient analysis of parallel conductors. As an example, the presented method is applied to evaluating the electromagnetic interference (EMI) to the shielded cable, whose shield is grounded at both ends, due to the switching operation in 500 kV air insulation substation (AIS). __________ Translated from Proceedings of the Chinese Society for Electrical Engineering, 2007, 27(9): 46–51 [译自: 中国电机工程学报]
Keywords:electromagnetic coupling  shielded cable  switching operation  substation
本文献已被 万方数据 SpringerLink 等数据库收录!