摘    要:This paper presented a model to predict the AC flashover voltage of contaminated suspension insulators.The prediction method is based on the maximum leakage current under AC operating voltage.Three kinds of widely used suspension insulators were tested in various contamination states such as pollution layers with different equivalent salt deposit density(ESDD),different composition of the conductive components,different non-soluble deposit density(NSDD) and different pollution distribution states to simulate the contamination states in nature.The effective ESDD was proposed and calculated.Influences of contamination states to maximum leakage current and flashover voltage were studied.Then,the relationships between flashover voltage and leakage current in these states were presented.Finally,considering the difference of insulator profiles,a new parameter is defined and a model to estimate the flashover voltage based on this parameter is developed.The model could be used in all kinds of suspension insulators in different contamination states and was validated by the test results.

关 键 词:flashover  voltage  suspension  insulators  leakage  current  pollution  layers  equivalent  salt  deposit  density(ESDD)  non-soluble  deposit  density(NSDD)

Prediction of Pollution Flashover Voltage Based on Leakage Current Under AC Operating Voltage
MEI Hongwei,WANG Liming,GUAN Zhicheng,MAO Yingke.Prediction of Pollution Flashover Voltage Based on Leakage Current Under AC Operating Voltage[J].High Voltage Engineering,2012(8):1924-1929.
Authors:MEI Hongwei  WANG Liming  GUAN Zhicheng  MAO Yingke
Affiliation:1.Graduate School at Shenzhen,Tsinghua University,Shenzhen 518055,China;2.Shanghai Extra High Voltage Power Transmission Company,Shanghai 200063,China)
Abstract:This paper presented a model to predict the AC flashover voltage of contaminated suspension insulators.The prediction method is based on the maximum leakage current under AC operating voltage.Three kinds of widely used suspension insulators were tested in various contamination states such as pollution layers with different equivalent salt deposit density(ESDD),different composition of the conductive components,different non-soluble deposit density(NSDD) and different pollution distribution states to simulate the contamination states in nature.The effective ESDD was proposed and calculated.Influences of contamination states to maximum leakage current and flashover voltage were studied.Then,the relationships between flashover voltage and leakage current in these states were presented.Finally,considering the difference of insulator profiles,a new parameter is defined and a model to estimate the flashover voltage based on this parameter is developed.The model could be used in all kinds of suspension insulators in different contamination states and was validated by the test results.
Keywords:flashover voltage  suspension insulators  leakage current  pollution layers  equivalent salt deposit density(ESDD)  non-soluble deposit density(NSDD)