首页 | 官方网站   微博 | 高级检索  
     

改进的特高压金属氧化物避雷器带电测试方法
引用本文:袁海燕,庄燕飞,任庆帅,于莎,李凯. 改进的特高压金属氧化物避雷器带电测试方法[J]. 电瓷避雷器, 2011, 0(6): 76-80
作者姓名:袁海燕  庄燕飞  任庆帅  于莎  李凯
作者单位:1. 山东电力研究院,济南,250002
2. 山东电力集团公司超高压公司,济南,250021
摘    要:在分析金属氧化物避雷器带电测试原理的基础上,提出在超特高压变电站中采用检修电源箱接线法进行避雷器带电测试的方法.通过理论和500 kV变电站现场试验的对比分析得出,PT二次接线法和检修电源箱接线法在避雷器带电测试中有相同的精确度,但PT二次接线法中需要取流过避雷器计数器的电流和电压互感器端子箱内的二次参考电压,比较适用...

关 键 词:特高压  金属氧化物避雷器  带电测试  检修电源箱

Improved Live Test Method for UHV MOA
YUAN Hai-yan,ZHUANG Yan-fei,REN Qing-shuai,YU Sha,LI Kai. Improved Live Test Method for UHV MOA[J]. Insulators and Surge Arresters, 2011, 0(6): 76-80
Authors:YUAN Hai-yan  ZHUANG Yan-fei  REN Qing-shuai  YU Sha  LI Kai
Affiliation:1.ShanDong Electric Power Research Institute,Jinan 250002,China;2.Extrahigh Power Subcompany of SEPCO.,Jinan 250021,China)
Abstract:Based on the analysis of live MOA testing principle,a new test method for live MOA in UHV substation using the maintenance power box wiring is proposed.Through the comparative analysis of theory and field testing in 500 kV substation,the conclusion is obtained that the methods of PT secondary wiring and maintenance power box wiring in live MOA testing have the same accuracy.However,the method of PT secondary wiring needs to get the current flowing through the arrester counter and the secondary reference voltage in the voltage transformer terminal box,and it is more suitable for low voltage live test.The method of maintenance power box wiring only needs to get the current flowing through the arrester counter and the reference voltage in maintenance power box,the the risk of false touch and wiring in gathering the secondary reference voltage in the voltage transformer is reduced,therefore,the maintenance power box wiring method can be applied in the field testing,especially for the MOA live test of 500 kV and above voltage level.
Keywords:UHV  MOA  live test  maintenance power box
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23