首页 | 官方网站   微博 | 高级检索  
     

苏州电网并网分布式电源防孤岛的继电保护控制策略研究
引用本文:范永宇,潘琪,姜臻,吴锋.苏州电网并网分布式电源防孤岛的继电保护控制策略研究[J].电力系统保护与控制,2017,45(2):94-98.
作者姓名:范永宇  潘琪  姜臻  吴锋
作者单位:江苏省电力公司苏州供电公司,江苏 苏州215000,江苏省电力公司苏州供电公司,江苏 苏州215000,广东电网公司珠海供电局,广东 珠海519000,江苏省电力公司苏州供电公司,江苏 苏州215000
摘    要:目前孤岛检测和防孤岛策略主要是基于并网分布式电源的特性而设计,而鲜有以孤岛发生时公用电网的电气特性为核心的继电保护防孤岛策略的研究。为了找到一种利用公用电网继电保护防孤岛的新方法,结合苏州电网,通过对孤岛形成机理的分析,找出了孤岛发生前后零序电压的变化规律。进而基于零序电压的变化规律设计了公用电网防孤岛的继电保护控制策略。数值仿真及苏州电网的防孤岛实例验证了该并网分布式电源防孤岛的继电保护控制策略的有效性。结果表明,该控制策略具有较高可靠性和实用前景。

关 键 词:并网分布式电源  零序电压  控制策略  公用电网继电保护  防孤岛
收稿时间:2016/7/31 0:00:00
修稿时间:2016/8/25 0:00:00

Research on the relay protection control strategy for anti-islanding of distributed generator connected to the power grid of Suzhou
FAN Yongyu,PAN Qi,JIANG Zhen and WU Feng.Research on the relay protection control strategy for anti-islanding of distributed generator connected to the power grid of Suzhou[J].Power System Protection and Control,2017,45(2):94-98.
Authors:FAN Yongyu  PAN Qi  JIANG Zhen and WU Feng
Affiliation:Suzhou Power Supply Company, Jiangsu Electric Power Company, Suzhou 215000, China,Suzhou Power Supply Company, Jiangsu Electric Power Company, Suzhou 215000, China,Zhuhai Power Supply Bureau, Guangdong Power Grid Company, Zhuhai 519000, China and Suzhou Power Supply Company, Jiangsu Electric Power Company, Suzhou 215000, China
Abstract:The present study on islanding and anti-islanding is mainly based on the characteristic of the distributed generator, however there is few research on anti-islanding by relay protection based on the electrical characteristics of the public power grid when islanding occurs. In order to find a new method which is using public power grid relay protection for anti-islanding, the analysis of the formation of islanding in Suzhou power grid is given, and the changing regulation of the zero-sequence voltage is then found. So the relay protection of public power grid for anti-islanding can be designed with zero-sequence voltage. The relay protection for anti-islanding of distributed generator is proved reasonable both by the simulation on PSCAD and the practical application of the strategy in power grid of Suzhou. The study proves that the relay protection strategy has high reliability and practical prospect.
Keywords:distributed generator connected to power grid  zero-sequence voltage  control strategy  relay protection of public power grid  anti-islanding
点击此处可从《电力系统保护与控制》浏览原始摘要信息
点击此处可从《电力系统保护与控制》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号