首页 | 官方网站   微博 | 高级检索  
     

基于PID-二分组合控制算法的分布参数空气源热泵仿真模型的研究
引用本文:龚光彩,李柏霖,周富玉,黄喜文. 基于PID-二分组合控制算法的分布参数空气源热泵仿真模型的研究[J]. 太阳能学报, 2022, 43(7): 16-21. DOI: 10.19912/j.0254-0096.tynxb.2020-1129
作者姓名:龚光彩  李柏霖  周富玉  黄喜文
作者单位:1.湖南大学土木工程学院,长沙 410082; 2.上海建筑设计研究院有限公司,上海 200040; 3.长沙房产有限公司,长沙 410082
基金项目:国家科技支撑计划(2015BAJ03B00);
摘    要:采用分布参数法建立双级压缩空气源热泵系统热力学模型,建立一种基于PID-二分组合控制算法的全系统循环分布参数模型,并结合实验数据验证该模型的准确性。结果表明:系统模型在双级压缩制热模式下制热性能系数(COP)的模拟数据与实验数据的平均偏差为5.41%,两者在不同运行模式下的最大偏差不超过15%,均在可信范围之内,模型能准确反映系统性能随外界参数变化的规律;该模型与单独使用比例积分微分(PID)控制算法的分布参数法模型相比,总迭代次数较原模型减少约2.96倍,极大减少了模型的计算量,可在保证模型精度的情况下提升模型的计算速度。

关 键 词:空气源热泵  热力学  仿真模拟  分布参数法  PID-二分组合控制算法  
收稿时间:2020-10-23

RESEARCH ON SIMULATION MODEL OF DISTRIBUTED PARAMETER AIR SOURCE HEAT PUMP BASED ON PID-BISECTION COMBINATION CONTROL ALGORITHM
Gong Guangcai,Li Bolin,Zhou Fuyu,Huang Xiwen. RESEARCH ON SIMULATION MODEL OF DISTRIBUTED PARAMETER AIR SOURCE HEAT PUMP BASED ON PID-BISECTION COMBINATION CONTROL ALGORITHM[J]. Acta Energiae Solaris Sinica, 2022, 43(7): 16-21. DOI: 10.19912/j.0254-0096.tynxb.2020-1129
Authors:Gong Guangcai  Li Bolin  Zhou Fuyu  Huang Xiwen
Affiliation:1. College of Civil Engineering, Hunan University, Changsha 410082, China; 2. Shanghai Architectural Design and Research Institute Co., Ltd., Shanghai 200040, China; 3. Changsha Real Estate (Group) Co., Ltd., Changsha 410082, China
Abstract:A two-stage compressed air source heat pump system thermodynamic model has been established in this paper by using distributed parameter method. Then we established a system-wide circulation distributed parameter model based on PID-binary combined control algorithm, and verified the accuracy of the model based on experimental data. The research results show that the average deviation between simulation data of COP and the experimental data of COP is 5.41% when the system model is operated in the two-stage compression heating mode. And the maximum deviation is under 15% in different operating modes. The deviations are all within the credible range, so the model can accurately reflect the law of system performance changing with external parameters. Comparing with the distributed parameter method model using only PID algorithm, the total iteration times of the model with using PID- bisection combined control algorithm are reduced by about 2.96 times. This model reduces computational effort greatly. The calculation speed of the model can be improved while ensuring the accuracy of the model.
Keywords:air source heat pumps  thermodynamics  computer simulation  distributed parameter method  PID-bisection combined control algorithm  
点击此处可从《太阳能学报》浏览原始摘要信息
点击此处可从《太阳能学报》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23