首页 | 官方网站   微博 | 高级检索  
     


Flashover voltage characteristics of contaminated station insulators under temporary ac overvoltages in the ac system connected with a frequency converter station
Authors:Takashi Yamazaki  Yoichi Takino  Ryosuke Matsuoka  Susumu Ito
Abstract:According to the recent analysis results of temporary ac overvoltage in the ac system connected with a frequency converter station, large-magnitude over-voltages were confirmed to occur under some special system conditions. Most of the station insulators currently used cannot withstand such overvoltages according to an evaluation based on the data obtained earlier. The necessity of tests to be done to evaluate such performance more accurately was recognized. Both power frequency and switching impulse overvoltage flashover tests were made on contaminated insulators by the method well simulating the natural wetting condition. Switching impulse flashover voltage with the waveshape having a long wavefront time of 2 ms can be well correlated with the flashover voltage characteristics of temporary ac overvoltage. Higher flashover voltage characteristics were obtained by a clean fog test method compared with those obtained by equivalent fog test method.
Keywords:Temporary ac withstand voltage  long wavefront switching impulse voltage  substation insulator