High impedance fault arcing on sandy soil in 15 kV distributionfeeders: contributions to the evaluation of the low frequency spectrum
Authors:Emanuel  AE Cyganski  D Orr  JA Shiller  S Gulachenski  EM
Affiliation:Worcester Polytech. Inst., MA;
Abstract:The measured values of current harmonics at a staged high-impedance ground fault on sandy soil are presented. The measured low-frequency spectrum is compared with current harmonics recorded continuously for one week at the substation. This comparison was carried out to determine to what extent 120 Hz and 180 Hz components can be used to help detect a high-impedance fault. The field measurements are supported by a simple theoretical model and laboratory measurements. It is concluded that, for the studied feeder, detection of high-impedance arcing faults may be possible by monitoring of the second-harmonic current