首页 | 官方网站   微博 | 高级检索  
相似文献
 共查询到20条相似文献,搜索用时 62 毫秒
1.
This paper presented a novel autocascade refrigeration cycle (NARC) with an ejector. In the NARC, the ejector is used to recover some available work to increase the compressor suction pressure. The NARC enables the compressor to operate at lower pressure ratio, which in turn improves the cycle performance. Theoretical computation model based on the constant pressure-mixing model for the ejector is used to perform a thermodynamic cycle analysis for the NARC with the refrigerant mixture of R23/R134a. The effects of some main parameters on cycle performance were investigated. The results show the NARC has an outstanding merit in decreasing the pressure ratio of compressor as well as increasing the COP. For NARC operated at the condenser outlet temperature of 40 °C, the evaporator inlet temperature of −40.3 °C, and the mass fraction of R23 is 0.15, the pressure ratio of the ejector reaches to 1.35, the pressure ratio of compressor is reduced by 25.8% and the COP is improved by 19.1% over the conventional autocascade refrigeration cycle.  相似文献   

2.
The occurrence of flow choking in an ejector of an ejector refrigeration system (ERS) was analysed and a model for predicting the maximum flow ratio of the ejector was developed. The multi-parameter equation to calculate the mass flow ratio takes into account the performance of the primary nozzle, the flow entrainment and mixing relating to ejector geometry and operating conditions. We validated the model using the reported experimental data of refrigerant R113, R141b and steam ERS. The present model was shown to provide better accuracy compared with results obtained by applying the existing 1-D ejector theory. We discussed the application of the model and highlighted the significance of the parameters for future work.  相似文献   

3.
A 1-D analysis for the prediction of ejector performance at critical-mode operation is carried out in the present study. Constant-pressure mixing is assumed to occur inside the constant-area section of the ejector and the entrained flow at choking condition is analyzed. We also carried out an experiment using 11 ejectors and R141b as the working fluid to verify the analytical results. The test results are used to determine the coefficients, ηp, ηs, φp and φm defined in the 1-D model by matching the test data with the analytical results. It is shown that the1-D analysis using the empirical coefficients can accurately predict the performance of the ejectors.  相似文献   

4.
A theoretical study of a novel regenerative ejector refrigeration cycle   总被引:1,自引:0,他引:1  
There has been a demand for developments of the ejector refrigeration systems using low grade thermal energy, such as solar energy and waste heat. In this paper, a novel regenerative ejector refrigeration cycle was described, which uses an auxiliary jet pump and a conventional regenerator to enhance the performance of the novel cycle. The theoretical analysis on the performance characteristics was carried out for the novel cycle with the refrigerant R141b. Compared with the conventional cycle, the simulation results show that the coefficient of performance (COP) of the novel cycle increases, respectively, by from 9.3 to 12.1% when generating temperature is in a range of 80–160 °C, the condensing temperature is in a range of 35–45 °C and the evaporating temperature is fixed at 10 °C. Especially due to the enhanced regeneration with increasing the pump outlet pressure, the improvement of COP of the novel cycle is approached to 17.8% compared with that in the conventional cycle under the operating condition that generating temperature is 100 °C, condensing temperature is 40 °C and evaporating temperature is 10 °C. Therefore, the characteristics of the novel cycle performance show its promise in using low grade thermal energy for the ejector refrigeration system.  相似文献   

5.
Jet-refrigeration cycles seem to provide an interesting solution to the increasing interest in environment protection and the need for energy saving due to their low plant costs, reliability and possibility to use water as operating fluid. A steam/steam ejector cycle refrigerator is investigated introducing a two-stage ejector with annular primary at the second stage. The steady_state refrigerator, exchanging heat with the water streams at inlet fixed temperatures at the three shell and tube heat exchangers, evaporator, condenser and generator, is considered as an open system. Heat transfer irreversibilities in the heat exchangers and external friction losses in the water streams are considered, ignoring the internal pressure drop of the vapor. A simulation program numerically searches the maximum COP at given external inlet fluid temperatures as a function of mass flows, dimensions and temperature differences in the heat exchangers. The code gives the ejector and heat exchangers design parameters.  相似文献   

6.
CFD analysis of ejector in a combined ejector cooling system   总被引:6,自引:1,他引:5  
One-dimensional ejector analyses often use coefficients derived from experimental data for a set of operating conditions with limited functionality. In this study, several ejector designs were modelled using finite volume CFD techniques to resolve the flow dynamics in the ejectors. The CFD results were validated with available experimental data. Flow field analyses and predictions of ejector performance outside the experimental range were also carried out. During validation, data from CFD predicted the entrainment ratios with greater accuracy on definite area ratios, although no shock was recorded in the ejector. Predictions outside the experimental range—at operating conditions in a combined ejector–vapour compression system—and flow conditions resulting from ejector geometry variations are discussed. It is found that the maximum entrainment ratio happens in the ejector just before a shock occurs and that the position of the nozzle is an important ejector design parameter.  相似文献   

7.
This paper describes a novel cycle which uses a steam ejector to enhance the concentration process by compressing the vapour from the lithium bromide solution to a state that it can be used to re-heat the solution from which it came. The energy efficiency and the performance characteristics of the novel cycle are theoretically investigated in this paper. The theoretical results show that the coefficient of performance (COP) of the novel cycle is better than the conventional single-effect absorption cycle. The characteristics of the cycle performance show its promise in using high temperature heat source at low cost.  相似文献   

8.
Experimental investigation on R134a vapour ejector refrigeration system   总被引:6,自引:1,他引:5  
The experimental investigation of the performance of a vapour ejector refrigeration system is described. The system uses R134a as working fluid and has a rated cooling capacity of 0.5 kW. The influence of generator, evaporator and condenser temperatures on the system performance is studied. This kind of system can be operated with low grade thermal energy such as solar energy, waste heat, etc. The operating conditions are chosen accordingly as, generator temperature between 338 K and 363 K, condenser temperature between 299 K and 310.5 K, and evaporator temperature between 275 K and 285.5 K. Six configurations of ejectors of different geometrical dimensions are selected for the parametric study. The performance of the refrigeration system at different operating temperatures is presented.  相似文献   

9.
This paper is a part in a series that reports on the experimental study of the performance of the two-phase ejector expansion refrigeration cycle. In the present study, three two-phase ejectors are used as an expansion device in the refrigeration cycle. The effects of throat diameter of the motive nozzle, on the coefficient of performance, primary mass flow rate of the refrigerant, secondary mass flow rate of the refrigerant, recirculation ratio, average evaporator pressure, compressor pressure ratio, discharge temperature and cooling capacity, which have never before appeared in open literature, are presented. The effects of the heat sink and heat source temperatures on the system performance are also discussed.  相似文献   

10.
In this paper, the performance of the solar-driven ejector refrigeration system with iso-butane (R600a) as the refrigerant is studied. The effects that both the operating conditions and the solar collector types have on the system's performance are also examined by dynamic simulation. The TRNSYS and EES simulation tools are used to model and analyze the performance of a solar-driven ejector refrigeration system. The whole system is modelled under the TRNSYS environment, but the model of the ejector refrigeration subsystem is developed in the Engineering Equations Solver (EES) program. A solar fraction of 75% is obtained when using the evacuated tube solar collector. In the very hot environment, the system requires relatively high generator temperature, thus a flat plate solar collector is not economically competitive because the high amount of auxiliary heat needed to boost up the generator temperature. The results from the simulation indicate that an efficient ejector system can only work in a region with decent solar radiation and where a sufficiently low condenser temperature can be kept. The average yearly system thermal ratio (STR) is about 0.22, the COP of the cooling subsystem is about 0.48, and the solar collector efficiency is about 0.47 at Te 15 °C, Tc 5 °C above the ambient temperature, evacuated collector area 50 m2 and hot storage tank volume 2 m3.  相似文献   

11.
This paper discusses the conservation of energy in a cogeneration system. A steam power cycle (Rankine) produces electrical power 2 MW and steam is bleeded off from the turbine at 7 bar to warm a factory or units of buildings during the winter or to supply a steam ejector refrigeration cycle to air-conditioning the same area during the summer. In the summer this system can be as alternative solution instead of absorption. Certainly the ejector refrigeration unit is more economical than absorption unit. The ratio of electrical power/heat is varied into the region (0.1–0.4) and the evaporator temperature of the ejector cycle is varied into the region (10–16 °C). A computer program has been developed for the study of performance parameters of the cogeneration system.  相似文献   

12.
This study presents experimental results obtained from a transcritical R744 system using a refrigerant ejector. The results were compared to that of a conventional system with an expansion valve. For the test conditions considered, the cooling capacity and COP simultaneously improved by up to 8% and 7%, respectively. Experiments were analyzed to quantitatively assess the effects on system performance as a result of changes in basic ejector dimensions such as motive nozzle and diffuser sizing. Small angles of 5° yielded best results for the static pressure recovery of the high-speed two-phase flow entering the diffuser. Experiments confirmed that like in a conventional transcritical R744 system with expansion valve, the high-side pressure control integrated into the ejector could be used to maximize the system performance. Numerical simulation results helped identifying this basic trend. Due to difficulties in the ejector throat pressure measurements, a more practical performance metric was introduced in order to quantify overall ejector efficiencies. According to this definition, the prototype ejector was able to recover up to 14.5% of the throttling losses.  相似文献   

13.
Ejector efficiencies for the primary nozzle, suction, mixing and diffuser were determined for the first time, according to their definitions, using an axi-symmetric CFD model. Water was considered as working fluid and the operating conditions were selected in a range that would be suitable for an air-conditioner powered by solar thermal energy. Ejector performance was estimated for different nozzle throat to constant section area ratios. The results indicated the existence of an optimal ratio, depending on operating conditions. Ejector efficiencies were calculated for different operating conditions. It was found that while nozzle efficiency can be considered as constant, the efficiencies related to the suction, mixing and diffuser sections of the ejector depend on operating conditions.  相似文献   

14.
A new combined power and refrigeration cycle is proposed for the cogeneration, which combines the Rankine cycle and the ejector refrigeration cycle by adding an extraction turbine between heat recovery vapor generator (HRVG) and ejector. This combined cycle could produce both power output and refrigeration output simultaneously, and could be driven by the flue gas from gas turbine or engine, solar energy, geothermal energy and industrial waste heats. Parametric analysis and exergy analysis are conducted to examine the effects of thermodynamic parameters on the performance and exergy destruction in each component for the combined cycle. The results show that the condenser temperature, the evaporator temperature, the turbine inlet pressure, the turbine extraction pressure and extraction ratio have significant effects on the turbine power output, refrigeration output, exergy efficiency and exergy destruction in each component in the combined cycle. It is also shown that the biggest exergy destruction occurs in the heat recovery vapor generator, followed by the ejector and turbine.  相似文献   

15.
Development of a circulating system for a jet refrigeration cycle   总被引:1,自引:0,他引:1  
This paper proposed a workless-generator-feeding (WGF) system for a jet refrigeration cycle, using R141b. This feeding system does not require any mechanical power. The liquid refrigerant from the condenser was fed to the vapour-generator by means of the generator pressure and gravitational force. The system was tested and compared with a conventional system using a mechanical pump. It was found that this system was workable. The heat input to the generator was slightly higher than that for a system using a mechanical pump. The jet refrigeration cycle employing this new feeding system provided a slightly lower coefficient of performance (COP) compared to a system using a mechanical pump. However, this new system did not require any mechanical energy. Therefore, the jet refrigeration system employing this WGF system is truly a heat-power refrigeration cycle.  相似文献   

16.
An ejector expansion transcritical CO2 refrigeration cycle is proposed to improve the COP of the basic transcritical CO2 cycle by reducing the expansion process losses. A constant pressure mixing model for the ejector was established to perform the thermodynamic analysis of the ejector expansion transcritical CO2 cycle. The effect of the entrainment ratio and the pressure drop in the receiving section of the ejector on the relative performance of the ejector expansion transcritical CO2 cycle was investigated for typical air conditioning operation conditions. The effect of different operating conditions on the relative performance of the ejector expansion transcritical CO2 cycle was also investigated using assumed values for the entrainment ratio and pressure drop in the receiving section of the ejector. It was found that the COP of the ejector expansion transcritical CO2 cycle can be improved by more than 16% over the basic transcritical CO2 cycle for typical air conditioning operation conditions.  相似文献   

17.
A cold generation system featuring a Rankine cycle powered refrigeration cycle actuated by a supersonic ejector was theoretically investigated in view of the thermo-fluid-dynamic optimization of the working fluid characteristics.

The ejector model was validated against well established performance charts relating to water. A reference system was considered in which a Rankine cycle at moderate top temperature delivers its expansion power by means of an ideal turbine to an ideal compressor of a refrigeration cycle. Two main optimizing variables were ascertained: the fluid critical temperature and the complexity of the fluid molecule. The best performance of such reference cycle is around 80% of that of an ideal fully reversible, Carnot cycle based, system (COP of 2.0 for tE,PC = 150 °C, tE,RC = 5 °C, and tC = 35 °C). As easily predictable the ejector compression introduces severe losses mainly due to the normal shock and the mixing of the motive and of the driven fluid. Overall COP for the above quoted temperatures decreases from 2.0 (reference cycle) to 0.4–0.7. The optimization of the working fluid showed that comparatively low critical temperatures are favoured and that a fluid complexity similar to that of CH5N or CH2Cl2 gives the best performance. A detailed losses analysis explains this behaviour. In particular at low reduced temperatures the theoretical gain related to the better shape in the T–S plane of both the power and the refrigeration cycle is more than offset by the higher ejector losses due to the stronger normal shock needed to cope with an increased pressure ratio.

Notwithstanding an extensive fluid screening we did not succeed in finding a fluid that could be considered optimum from all points of view including ambient and safety issues. However, a number of traditional (non-zero ODP) chloro-fluoro-carbons and of new (zero ODP) refrigerants were found that yield, on the whole, a satisfactory performance.

Provided calculated COP will be confirmed by experimental testing, ejector powered refrigerators could compete with absorption systems in many applications.  相似文献   


18.
CO2 is environmentally friendly, safe and more suitable to ejector refrigeration cycle than to vapor compression cycle. Supersonic two-phase flow of CO2 in the diverging sections of rectangular converging–diverging nozzles was investigated. The divergence angles with significant variation of decompression were 0.076°, 0.153°, 0.306° and 0.612°. This paper presents experimental decompression phenomena which can be used in designing nozzles and an assessment of Isentropic Homogeneous Equilibrium (IHE). Inlet conditions around 6–9 MPa, 20–37 °C were used to resemble ejector nozzles of coolers and heat pumps. For inlet temperature around 37 °C, throat decompression boiling from the saturated liquid line, supersonic decompression and IHE solution were obtained for the two large divergence angles. For divergence angles larger than 0.306°, decompression curves for inlet temperature above 35 °C approached IHE curves. For divergence angles smaller than 0.306° or for nozzles with inlet temperature below 35 °C, IHE had no solution.  相似文献   

19.
A theoretical investigation was performed concerning the coefficient of performance (COP) of cascade refrigerating systems using N2O as refrigerant for the low temperature cascade stage and various natural refrigerants like ammonia, propane, propene, carbon dioxide and nitrous oxide itself for the high temperature stage. The basis of the comparison was a conventional R23/R134a-cascade refrigerating system for heat rejection temperatures of +55, +35 and +25 °C for air cooling, cooling tower water cooling and city water cooling, respectively. It can be stated that such an application of N2O at the primary stage and ammonia or hydrocarbons as refrigerants at the secondary stage in refrigerating systems achieves similar COP-values compared to the R23/R134a-cascade refrigerating system, whereas CO2 and N2O in a transcritical cycle in general perform worse.An application of N2O in a two-stage compression cycle with interstage injection and city water cooling at low and high interstage temperatures has a nearly equal COP as a conventional R23/R134a-cascade refrigerating system and is an interesting alternative for small laboratory refrigerating systems.  相似文献   

20.
In the present study, two empirical correlations from the test results of 15 ejectors are derived for the performance prediction of ejectors using R141b as the working fluid. The ratio of the hypothetical throat area of the entrained flow to the nozzle throat area Ae/At, the geometric design parameter of the ejector A3/At, and the pressure ratios Pg/Pe and Pc*/Pe are used to correlate the performance of the ejector. The prediction of the entrainment ratio ω using the correlations is within ±10% error. A method of calculation for the ejector design using the correlations is also developed. R141b is shown in the present study to be a good working fluid for an ejector. The measured ω for the ejectors used in the present study can reach as high as 0.54 at Pg=0.465 MPa (84°C), Pc*=0.087 MPa (28°C) and Pe=0.040 MPa (8°C). For Pg=0.538 MPa (90°C), Pc*=0.101 MPa (32°C) and Pe=0.040 MPa (8°C), ω reaches 0.45.

Résumé

Dans cette étude, on a établi deux corrélations empiriques à partir des résultats expérimentaux obtenus utilisant 15 éjecteurs; ces corrélations ont été utilisées ensuite pour prédire la performance d'éjecteurs utilisant le R141b comme fluide frigorigène. Les rapports Ae/At (section de passage du fluide entraîné rapporté à la section théorique du col de l'éjecteur), et A3/At (section de sortie de l'éjecteur rapporté à la section théorique du col de l'éjecteur) et les relations entre pressions Pg/Pe et Pc*/Pe sont utilisés pour trouver la corrélation de la performance de l'éjecteur. La prévision du taux d'entraînement à partir des corrélations est précise à la hauteur de ±10%. Les auteurs ont également développé une méthode de calcul permettant de concevoir des éjecteurs à partir des corrélations. On a montré dans cette étude que le R141b s'avère être un fluide actif efficace pour cette utilisation. Le ω mesuré des éjecteurs utilisés dans cette étude peuvent atteindre 0.54 à Pg=0.465 MPa (84°C), Pc*=0.087 MPa (28°C) et Pe=0.040 MPa (8°C). Pour Pg=0.538 MPa (90°C), Pc*=0.101 MPa (32°C) et Pe=0.040 MPa (8°C), ω atteint 0.45.  相似文献   