1.
In this article, an experimental investigation is performed to measure the boiling heat transfer coefficient of water flow in a microchannel with a hydraulic diameter of 500 μm. Experimental tests are conducted with heat fluxes ranging from 100 to 400 kW/m2, vapor quality from 0 to 0.2, and mass fluxes of 200, 400, and 600 kg/m2s. Also, this study has modified the liquid Froude number to present a flow pattern transition toward an annular flow. Experimental results show that the flow boiling heat transfer coefficient is not dependent on mass flux and vapor quality but on heat flux to a certain degree. The measured heat transfer coefficient is compared with a few available correlations proposed for macroscales, and it is found that previous correlations have overestimated the flow boiling heat transfer coefficient for the test conditions considered in this work. This article proposes a new correlation model regarding the boiling heat transfer coefficient in mini- and microchannels using boiling number, Reynolds number, and modified Froude number.  相似文献   

2.
 对用于固体激光介质冷却的组合式中间换热器的流动与传热特性进行了实验研究。实验研究结果表明:努塞尔数随雷诺数的增加而增加,总热阻随微通道侧蒸馏水流量的增加而减小,总换热量随微通道侧蒸馏水流量的增加而增加,且换热器的传热系数可以达到1.5×104 W/(m2·K),总热阻小于0.3 K/W,能较好地解决当前固体激光介质冷却系统中间换热器所存在的问题。  相似文献   

3.
Presented are results of an experimental study of local heat transfer characteristics in boiling of the dielectric liquid perfluorohexane under forced convection in a horizontal microchannel heat exchanger. The experiments with a copper microchannel heat exchanger comprising 21 channels with sections of 335 × 930 μm were conducted with a mass velocity of 250 to 1000 kg/m2s and a heat flux through the outer wall of the heat exchanger of 3 to 60 W/cm2. The dependence of the local heat transfer coefficient on the heat flux density on the inner wall of the microchannels was established, as well as the critical heat flux. The experimental data are compared with calculations based on known models of heat transfer.  相似文献   

4.
波纹板式空冷器阻力与传热特性实验研究   总被引:5,自引:0,他引:5  
在可改变风量和热水流量的实验条件下,对波纹板式空冷器的阻力与传热特性进行实验研究。得到了空气侧的阻力降关联式以及两侧的对流换热系数关联式,其适用于热水雷诺数在2000-8000之间、空气雷诺数在2000-10000之间。在相同工况下,比较了波纹板式、光管式和翅片管式空冷器的性能指标,结果表明:迎面风速在2.45-4.1 m/s之间,波纹板式空冷器传热系数达到100-160 W/m2/℃;约比光管式提高70%,但只有以管束外表面为基准的翅片管式传热系数的六分之一;板式空冷器单位体积换热量约是翅片管式空冷器的1.5倍,是光管式的15倍;板式空冷器单位功耗换热量约是光管式空冷器的5.5倍,而翅片管式空冷器与光管式空冷器则相差不大。  相似文献   

5.
K. Koyama  Y. Asako 《实验传热》2013,26(2):130-143
Heat transfer characteristics of a gas-to-gas counterflow microchannel heat exchanger have been experimentally investigated. Temperatures and pressures at inlets and outlets of the heat exchanger have been measured to obtain heat transfer rates and pressure drops. The heat transfer and the pressure drop characteristics are discussed. Since the partition wall of the heat exchanger is thick compared with the microchannel dimensions, a simple heat exchange model with constant wall temperature is proposed to predict the heat transfer rate. The predicted heat transfer rate using the constant wall temperature model agrees well with the experimental results.  相似文献   

6.
An experimental investigation has been carried out to study the enhancement in heat transfer coefficient by inserting coiled wire around the outer surface of the inner tube of the double-pipe heat exchanger. Insulated wires, with a circular cross-section of 2 mm diameter, forming a coil of different pitches (p = 6, 12, and 20 mm), were used as turbulators. The investigation is performed for turbulent water flow in a double-pipe heat exchanger with cold water in the annulus space for both parallel and counter flows. The experiments were performed for Reynolds numbers ranging from 4,000 to 14,000. The experimental results reveal that the use of coiled circular wires leads to a considerable increase in heat transfer coefficients compared with a smooth wall tube for both parallel and counter water flows. The mean Nusselt number increases with Reynolds number and pitch. The convective heat transfer coefficient for a turbulent water flow increases for all coiled wire pitches, with the highest enhancement of about 450% for counter flow and 400% for the parallel flow. New correlations for mean relative Nusselt numbers at different coiled wire pitches are provided.  相似文献   

7.
G. Arslan  N. Eskin 《实验传热》2015,28(5):430-445
In this study, condensation of pure refrigerant R134a vapor inside a smooth vertical tube was experimentally investigated. The test section was made of a copper tube with inside diameter of 7.52 mm and length of 1 m. Experimental tests were conducted for mass fluxes in the range of 20–175 kg/m2s with saturation pressure ranging between 5.8 and 7 bar. The effects of mass flux, saturation pressure, and temperature difference between the refrigerant and tube inner wall (ΔT) on the heat transfer performance were analyzed through experimental data. Obtained results showed that average condensation heat transfer coefficient decreases with increasing saturation pressure or temperature difference (ΔT). In addition, for the same temperature difference (ΔT), heat can be removed from the refrigerant at a higher rate at relatively low pressure values. Under the same operating conditions, it was shown that average condensation heat transfer coefficient increases as mass flux increases. Finally, the most widely used heat transfer coefficient correlations for condensation inside smooth tubes were analyzed through the experimental data. The best fit was obtained with Akers et al.'s (1959) correlation with an absolute mean deviation of 22.6%.  相似文献   

8.
Enhancement of heat transfer in a heat exchanger via a DC corona discharge was studied experimentally using a single-tube shell-and-tube heat exchanger. Air was the working fluid in both the tube and shell sides. Excitation of the tube side was via a single wire electrode, while that of the shell side was via four rod electrodes oriented symmetrically at 90° intervals. Three series of experiments were performed: (1) excitation of the tube side only, (2) excitation of the shell side only, and (3) simultaneous excitation of the tube and shell sides. Both heat transfer and pressure drop measurements were performed, with Reynolds number and electric field potential as parametric quantities in the tube and shell sides. It was found that highest enhancements take place when the tube and shell sides are excited simultaneously, yielding a 322% increase in the overall heat transfer coefficient. Study of the heat transfer enhancements per unit pumping power indicates that for the range of parameters studied, the technique is most efficient at moderate Reynolds numbers and at electrode potentials in the midrange between threshold and sparkover limits.  相似文献   

9.
Forced convection heat transfer from a helically coiled heat exchanger embedded in a packed bed of spherical glass particles was investigated experimentally. With dry air at ambient pressure and temperature as a flowing fluid, the effect of particle size, helically coiled heat exchanger diameter, and position was studied for a wide range of Reynolds numbers. It was found that the particle diameter, the helically coiled heat exchanger diameter and position, and the air velocity are of great influence on the convective heat transfer between the helically coiled heat exchanger and air. Results indicated that the heat transfer coefficient increased with increasing the air velocity, increasing helically coiled heat exchanger diameter, and decreasing the particle size. The highest heat transfer coefficients were obtained with the packed-bed particle size of 16 mm and heat exchanger coil diameter of 9.525 mm (1/4 inch) at a Reynolds number range of 1,536 to 4,134 for all used coil positions in the conducted tests. A dimensionless correlation was proposed for Nusselt number as a function of Reynolds number, particle size, coil size, and coil position.  相似文献   

10.
This article experimentally and numerically analyzes the effect of turbulators with different geometries (Type I, Type II, Type III, and Type IV) located at the inlet of the inner pipe in a concentric-type heat exchanger. Experiments were performed at parallel-flow conditions in the same and opposite directions to investigate the impact of manufactured turbulators on heat transfer and pressure drop. In the numerical study, ANSYS 12.0 Fluent code program was used, and basic protection equations were solved in the steady-state, three-dimensional, and turbulence-flow conditions. Results were obtained from numerical analysis conducted at different flow values of air (7, 8, 9, 10, 11, and 12 m3/h). The distribution of temperature, velocity, and pressure was demonstrated as a result of numerical analyses. Experimental and numerical results were compared, and it was observed that they were in conformity with each other. When the data obtained from the analyses were examined, the highest heat transfer, pressure drop, and friction factor increase were detected to be in the Type IV turbulator.  相似文献   

11.
Thermal performance of a latent heat storage unit is evaluated experimentally. The latent heat thermal energy storage system analyzed in this work is a shell-and-tube type of heat exchanger using paraffin wax (melting point between 58°C and 60°C) as the phase change material. The temperature distribution in the phase change material is measured with time. The influence of mass flow rate and inlet temperature of the heat transfer fluid on heat fraction is examined for both the melting and solidification processes. The mass flow rate of heat transfer fluid (water) is varied in the range of 0.0167 kg/s to 0.0833 kg/s (1 kg/min to 5 kg/min), and the fluid inlet temperature is varied between 75°C and 85°C. The experimental results indicate that the total melting time of the phase change material increases as the mass flow rate and inlet temperature of heat transfer fluid decrease. The fluid inlet temperature influences the heat fraction considerably as compared to the mass flow rate of heat transfer fluid during the melting process of the phase change material.  相似文献   

12.
传统弓形折流板换热器壳程流体横向流动时存在流动阻力和传热死区大等缺点。为克服上述不足,研究开发了一种新型高效节能的斜向流管壳式换热器,采用导向型折流栅替代传统弓形折流板,倾斜流道内流体斜向冲刷换热管束。考察和对比了斜向流换热器和弓形折流板换热器壳程主流区的流体流速分布和变化规律,证实了导向型折流栅具有显著的控涡均化壳程流场和提高壳程流体整体流速的作用,有助于减小壳程压降,增大有效换热面积,为管壳式换热器结构改良提供了参考依据。  相似文献   

13.
C. Zhang  Y. Han  Y. Zhu  X. Peng 《实验传热》2017,30(2):162-177
There has been increased attention on various types of plate heat exchangers because of their high efficiency and compactness. This article presents an investigation of heat transfer and fluid flow performance of a novel plate heat exchanger based on numeric studies and experimental tests. Parameters of the novel plate heat exchanger are analyzed and discussed. The thermo-hydraulic transfer performance of different plate heat exchangers is comprehensively analyzed using the exergy and entransy principle. The results indicate that the novel plate heat exchanger has better thermo-hydraulic transfer performance than the smooth plate heat exchanger. The result of this study provides a paradigm for the optimal design of plate heat exchangers.  相似文献   

14.
This study reports an experimental investigation of evaporative heat transfer and pressure drop of R-134a flowing downward inside vertical corrugated tubes with different corrugation pitches. The double tube test section is 0.5 m long with refrigerant flowing in the inner tube and hot water flowing in the annulus. The inner tubes are comprised of one smooth tube and three corrugated tubes with different corrugation pitches of 6.35, 8.46, and 12.7 mm. The test runs are performed at evaporating temperatures of 10°C, 15°C, and 20°C; heat fluxes of 20, 25, and 30 kW/m2; and mass fluxes of 200, 300, and 400 kg/m2s. The experimental data obtained from the smooth tube are plotted with flow pattern map for vertical flow. Comparisons between smooth and corrugated tubes on the heat transfer and pressure drop are also discussed. It is observed that the heat transfer coefficient and frictional pressure drop obtained from the corrugated tubes are higher than those from the smooth tube. Furthermore, the heat transfer coefficient and frictional pressure drop increase as the corrugation pitch decreases. The maximum heat transfer enhancement factor and penalty factor are up to 1.22 and 4.0, respectively.  相似文献   

15.
螺旋折流片换热器壳侧传热与流动的数值模拟   总被引:9,自引:1,他引:8  
提出了一种强化管壳式换热器壳侧传热的螺旋折流片式换热器新方案,该方案在部分管子上套上螺旋折流片,不仅强化传热,而且对相邻管子形成支撑;利用FLUENT流体计算软件对同心套管螺旋折流片式换热段的壳侧流场、温度场进行了数值模拟,并讨论了螺旋角对其强化传热和阻力性能的影响。结果显示螺旋折流片诱导的涡旋流动对于减薄边界层,促进近壁流体与主流区流体的动量和质量交换进而强化传热有明显的作用,传热系数可比光管提高约40%-100%,但其流动阻力也将增大。  相似文献   

16.
An experimental energy storage system has been designed using a new type flat micro heat pipe heat exchanger that incorporates a moderate-temperature phase change material paraffin with a melting point of 58°C. The basic structure, working principles, and design concept are discussed. The heat transfer process during the charging and discharging of the heat exchanger under various operating conditions has been experimentally investigated. Results show that the performance of the new type flat micro heat pipe was steady and efficient during charging and discharging. The average thermal storage power and absorption efficiency have been determined to be approximately 537 W and 92.5%, respectively.  相似文献   

17.
An experimental study of condensation heat transfer characteristics of flow inside horizontal micro-fin tubes is carried out using R410A, R22, and R32 as the test fluids. This study especially focuses on the influence of heat transfer area upon the condensation heat transfer coefficients. The test sections were made of double tubes using the counter-flow type; the refrigerants condensation inside the test tube enabled heat to exchange with cooling water that flows from the annular side. The saturation temperature and pressure of the refrigerants were measured at the inlet and outlet of the test sections to defined state of refrigerants, and the surface temperatures of the tube were measured. A differential pressure transducer directly measured the pressure drops in the test section. The heat transfer coefficients and pressure drops were calculated using the experimental data. The condensation heat transfer coefficient was measured at the saturation temperature of 48°C with mass fluxes of 50–380 kg/(m2s) and heat fluxes of 3–12 kW/m2. The values of experimental heat transfer coefficient results are compared with the predicted values from the existing correlations in the literature, and a new condensation heat transfer coefficient correlation is proposed.  相似文献   

18.
对倾斜角为20°、24°、28°和32°的单头以及32°的双头周向重叠三分螺旋折流板换热器和弓形折流板换热器的传热和压降性能进行了测试,换热器采用公共壳体和可更换管芯结构。采用壳侧轴向雷诺数和轴向欧拉数分别作为反映壳侧流量和阻力系数的无因次参数。试验结果显示在试验范围内周向重叠三分螺旋折流板换热器壳侧换热系数、壳侧压降和综合性能指标都随着倾斜角增大而减小;倾斜角20°方案的性能指标最佳,其平均壳侧努塞尔数和轴向欧拉数与弓形折流板方案的数值之比分别为1.123和0.45;双头螺旋折流板方案的换热系数和压降都大于同样倾斜角的单头螺旋折流板方案,但两者的综合性能较接近。  相似文献   

19.
In the present study, convective heat transfer to the air from a heating tube attached to conical baffles with rift was experimentally examined. The air entering the test section first contacts the large surface of the conical baffle. Therefore, the conical baffle both directs the air toward the heating surface and increases the heat transfer surface area. In the experiments, baffles with inclination angles of 45°, 60°, and 80° were used. The baffles were placed on the heating tube at the pitch of 15 mm. The temperature of the heating fluid (water) was kept fixed at 65°C. In addition to the riftless baffles, the experiments were carried out by using baffles with a rift spacing of 1.5 and 3.5 mm so that the boundary layer separation mechanism could be accelerated. Experimental results for eight different velocities of airflow (2–20 m/s) were presented. For the inclination angle of 60°, the increase in the heat transfer of the baffle with rift was 13% at a rift spacing of 1.5 mm and 4% at a rift spacing of 3.5 mm according to the riftless baffle. In addition, for the inclination angle of 60°, the pressure drop values of the riftless and the rift spacing of 1.5 and 3.5 mm were almost the same.  相似文献   

20.
弓形折流板换热器中折流板对换热器性能的影响   总被引:2,自引:0,他引:2  
本文采用Bell-Delaware换热器设计方法研究了传统弓形折流板换热器加热轻油时在不同管束排列角度下,改变换热器壳侧折流板间距以及改变折流板的窗口高度对管壳式换热器的壳体内径、换热管数目、壳侧换热系数及壳侧压降的影响.  相似文献   