Energy performance optimization of radiant slab cooling using building simulation and field measurements |
| |
Authors: | Zhen Tian James A Love |
| |
Affiliation: | Faculty of Environmental Design, University of Calgary, 2500 University Drive, N.W., Calgary, AB, Canada T2N 1N4 |
| |
Abstract: | Few field studies of energy performance of radiant cooling systems have been undertaken. A recently constructed 17,500 m2 building with a multi-floor radiant slab cooling system in the tower was investigated through simulation calibrated with measured building energy use and meteorological data. For the very cold, dry region where the building was located, it was found that a typical floor of the tower would have had 30% lower annual energy use with a conventional variable air volume system than with the as-built radiant cooling-variable air volume combination. This was due to (1) simultaneous heating and cooling by the existing radiant cooling and air systems, (2) the large amount of free cooling possible in this climate, and (3) suboptimal control settings. If these issues were remedied and combined with improved envelope and a dedicated outdoor air system with exhaust air heat recovery, a typical floor could achieve annual energy use 80% lower than a typical floor of the existing building HVAC system. This shows that radiant thermal control can make a significant contribution to energy-efficiency, but only if the building design and operating practices complement the strengths of the radiant system. |
| |
Keywords: | Building energy performance Radiant cooling Simulation EnergyPlus Measurement and verification |