首页 | 官方网站   微博 | 高级检索  
     

水源热泵系统回灌量衰减的监测与分析
引用本文:杨,帆,孟,杉,张红梅.水源热泵系统回灌量衰减的监测与分析[J].山西建筑,2014(9):151-153.
作者姓名:        张红梅
作者单位:北京市地质工程勘察院,北京100048
摘    要:为了解决水源热泵系统回灌过程中出现的问题,选择典型项目开展回灌监测工作,通过对各井水位、水量的监测,获得了7年的监测数据,确定了各井的回灌能力,监测结果表明:项目运行的前3年回灌系统处于最佳工作状态,但系统运行6年后,各井回灌量累计衰减超过60%。

关 键 词:水源热泵  回灌量  水位  监测

Attenuation detection and analysis during reinjection of water source heat pump system
YANG Fan,MENG Shan,ZHANG Hong-mei.Attenuation detection and analysis during reinjection of water source heat pump system[J].Shanxi Architecture,2014(9):151-153.
Authors:YANG Fan  MENG Shan  ZHANG Hong-mei
Affiliation:( Beijing Institute of Geological Engineering, Beijing 100048, China)
Abstract:This paper chooses a typical project to make a monitoring plan. After 7 years' monitoring, all the recharge wells' water level and the quality of water has been recorded after every running season. It is used to determine every wells' recharge capacity. The result shows the first 3 years the recharge system was at an optimal state. However after the system running 6 years, the well recharge has decreased over 60%.
Keywords:water source heat pump  recharge  mater level  detection
本文献已被 CNKI 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号