宁波南苑饭店扩建工程空调设计
引用本文:朱军.宁波南苑饭店扩建工程空调设计[J].暖通空调,2004,34(12):86-88,112.
作者姓名:朱军
作者单位:宁波市机电工业研究设计院
摘    要:介绍了风系统和水系统的设计。商务套房采用空气源热泵作为冷热源,为便于分户计量,装设了集中空调计费系统,以每台风机盘管上安装的采样器采集到的时间当量为计费依据。大会议厅采用自动调节型条缝风口吊顶送风,风口截面大小可随送风温度自动调节。为防止室内游泳馆窗玻璃结露,在窗子上方设条缝型风口沿玻璃面送热风。

关 键 词:空调设计  风口  游泳馆  吊顶  风系统  送风  分户计量  饭店  宁波  商务

Air conditioning system design for extension of Nanyuan Hotel in Ningbo
By Zhu Jun Ningbo Research Design Institute of Mechanical-Electrical Industry,Ningbo,Zhejiang Province,China.Air conditioning system design for extension of Nanyuan Hotel in Ningbo[J].Journal Heating Ventilating and Airconditioning,2004,34(12):86-88,112.
Authors:By Zhu Jun Ningbo Research Design Institute of Mechanical-Electrical Industry  Ningbo  Zhejiang Province  China
Abstract:Presents the design of the air supply and return system and the water system. The business suites take air-source heat pumps as cold and heat sources, and for individual metering, adopt the central air conditioning metering and charging system based on time equivalent from the sampler on each fan-coil unit. The large conference hall adopts ceiling air supply mode with self-regulation slot outlets whose area could automatically vary with supply air temperature. To avoid condensation on the window glass of the indoor swimming pool, sets up the slot outlet on the upper part to supply heat air to the glass surface.
Keywords:hotel  air conditioning  air supply and return system  water system  metering and charging system  slot outlet  