首页 | 官方网站   微博 | 高级检索  
     


Study of a novel silica gel–water adsorption chiller. Part I. Design and performance prediction
Authors:DC Wang  ZZ Xia  JY Wu  RZ Wang  H Zhai  WD Dou
Affiliation:aInstitute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai 200030, China;bJiangsu Shuangliang Air Conditioning Equipment Co. Ltd, Jiangsu 214444, China
Abstract:A novel silica gel–water adsorption chiller is designed and its performance is predicted in this work. This adsorption chiller includes three vacuum chambers: two adsorption/desorption (or evaporation/condensation) vacuum chambers and one heat pipe working vacuum chamber as the evaporator. One adsorber, one condenser and one evaporator are housed in the same chamber to constitute an adsorption/desorption unit. The evaporators of two adsorption/desorption units are combined together by a heat-pipe heat exchanger to make continuous refrigerating capacity. In this chiller, a vacuum valve is installed between the two adsorption/desorption vacuum chambers to increase its performance especially when the chiller is driven by a low temperature heat source. The operating reliability of the chiller rises greatly because of using fewer valves. Furthermore, the performance of the chiller is predicted. The simulated results show that the refrigerating capacity is more than 10 kW under a typical working condition with hot water temperature of 85 °C, the cooling water temperature of 31 °C and the chilled water inlet temperature of 15 °C. The COP exceeds 0.5 even under a heat source temperature of 65 °C.
Keywords:Design  Adsorption system  Water  Silica gel  PerformanceMots clé  s: Conception  Systè  me à  adsorption  Eau  Gel de silice  Performance
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号