首页 | 官方网站   微博 | 高级检索  
     

模块化UPS并联的新型数字均流控制技术
引用本文:单鸿涛,KANG Yong,康勇,段善旭,张宇,余蜜,刘永桥,陈国英.模块化UPS并联的新型数字均流控制技术[J].高电压技术,2008,34(2):289-292.
作者姓名:单鸿涛  KANG Yong  康勇  段善旭  张宇  余蜜  刘永桥  陈国英
作者单位:1. 华中科技大学电气与电子工程学院,武汉,430074;湖北汽车工业学院电气工程系,十堰,442002
2. 华中科技大学电气与电子工程学院,武汉,430074
3. 深圳艾默生网络能源有限公司,深圳,518057
基金项目:国家自然科学基金(50237020)~~
摘    要:为实现并联UPS系统中负载电流的均分和环流的抑制,阐述了一种应用于模块化UPS并联系统的数字化控制均流技术。给出了并联系统的结构;通过分析并联系统环流、功率调节特性、并联系统数字功率检测技术,得到一种新型的功率检测方法;检测和分析并联系统的瞬时平均电流和各个UPS模块输出电流,再反馈调节分别控制输出电压幅值和相位以实现其均流控制。实验证明该环流抑制控制策略可获得良好的并联均流特性,方案简洁、实用。

关 键 词:UPS  并联  环流  数字控制  功率检测  均流控制
文章编号:1003-6520(2008)02-0289-04
收稿时间:2007-04-18
修稿时间:2007年4月18日

Novel Digital Parallel Current Sharing Control Technique of Modularized UPS
KANG Yong.Novel Digital Parallel Current Sharing Control Technique of Modularized UPS[J].High Voltage Engineering,2008,34(2):289-292.
Authors:KANG Yong
Affiliation:1(1. College of Electrical and Electronics Engineering, Huazhong University of Science and Technology, Wuhan 430074, China; 2. Department of Electrical Engineering, Huibei Automobile Industrial Institute, Shiyan 442002, China; 3. Emerson Network Power Co., Ltd., Shenzhen 518057, China)
Abstract:In order to share the load and restrain circumfluence, a digital current sharing control technique for modularized UPS parallel operation is investigated in detail, and the structure of parallel system is presented. The modularized UPS parallel operation uses the distributed-logical-control, where each parallel operating inverter is at equal position in the parallel system. So it has better reliability. Based on the analysis of circumfluence of paralleled system, characteristics of the power regulation and a novel digital power detection technique are deduced. With measuring and analyzing the instantaneous average current of all modules and the output current of each UPS module in the parallel system, both of current components are used to feedback control and regulate the amplitude and the phase of the output voltage with DSP controller. In this way, the control of current sharing in the modularized UPS paralleling system is realized. The proposed current sharing control technique and the good characteristic of restraining circumfluence were verified by the experimental results. The control strategy has advantages of simple, high practicality.
Keywords:UPS  parallel  circumfluence  digital control  power detection  current sharing control
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号