1000 kV特高压输电线路的电磁环境
引用本文:邵方殷.1000 kV特高压输电线路的电磁环境[J].电网技术,2007,31(22):1-6.
作者姓名:邵方殷
作者单位:中国电力科学研究院,北京市,海淀区,100085
摘    要:输送相同功率时,对采用1000 kV特高压输电和5回500 kV输电所需线路走廊及其电磁环境作了对比分析,分析结果说明:1 000 kV特高压输电较5回500 kV输电所需的线路走廊可节省98~111 m;工频电场、工频磁场、无线电干扰和可听噪声的影响范围也大为减小。

关 键 词:特高压输电线路  线路走廊  电磁环境
文章编号:1000-3673(2007)22-0001-06
修稿时间:2007-07-05

Electromagnetic Environment of 1000kV UHV Transmission Line
SHAO Fang-yin.Electromagnetic Environment of 1000kV UHV Transmission Line[J].Power System Technology,2007,31(22):1-6.
Authors:SHAO Fang-yin
Affiliation:China Electric Power Research Institute, Haidian District, Beijing 100085, China
Abstract:Comparison and analysis on transmission corridor for 1000 kV transmission line and those for fivecircuit 500 kV transmission lines as well as the two electromagnetic environment are performed. Analysis results show that under the same transmitted power, the width of transmission corridor for 1000 kV transmission line can be narrowed dwwn in the range from 98m to 110m than total width of corridors for five-circuit 500 kV transmission lines; meanwhile the effected ranges of power frequency electric field and magnetic field, radio interference and audible noise are evidently decreased.
Keywords:UHV transmission line  transmission corridor  electromagnetic environment
本文献已被 维普 万方数据 等数据库收录!