南方电网在线稳定分析中的动态等值方案
引用本文:赵良,张文朝,马世英,曾勇刚,黄河,苏寅生.南方电网在线稳定分析中的动态等值方案[J].电网技术,2008,32(6):31-35.
作者姓名:赵良  张文朝  马世英  曾勇刚  黄河  苏寅生
作者单位:1. 中国电力科学研究院,北京市,海淀区,100192
2. 中国南方电网电力调度通信中心,广东省,广州市,510623
摘    要:针对南方电网离线和在线稳定计算数据之间存在较大差异的情况,分析了同时忽略一定规模的发电机和负荷、忽略220 kV电网数据、负荷从110 kV侧移置220 kV侧以及忽略香港电网等因素对南方电网在线稳定分析结果的影响,对合理扩大监视控制与数据采集/能量管理系统的在线数据采集规模提出建议。利用动态等值技术提出了对应南方电网目前在线数据规模和建议发展规模的等值方案,从潮流分布、短路电流、典型故障分析等方面对2个方案进行了比较分析,表明推荐方案在保留系统稳定特性方面具备更好的适应性。

关 键 词:南方电网  动态等值  在线分析  监视控制与数据采集系统  能量管理系统
文章编号:1000-3673(2008)06-0031-05
收稿时间:2007-08-17
修稿时间:2007年8月22日

Dynamic Equivalence Schemes of Southern China Power Grid for On-Line Stability Analysis
ZHAO Liang,ZHANG Wen-chao,MA Shi-ying,ZENG Yong-gang,HUANG He,SU Yin-sheng.Dynamic Equivalence Schemes of Southern China Power Grid for On-Line Stability Analysis[J].Power System Technology,2008,32(6):31-35.
Authors:ZHAO Liang  ZHANG Wen-chao  MA Shi-ying  ZENG Yong-gang  HUANG He  SU Yin-sheng
Affiliation:1.China Electric Power Research Institute,Haidian District,Beijing 100192,China; 2.CSG Power Dispatching and Communication Center,Guangzhou 510623,Guangdong Province,China
Abstract:In view of the evident difference between the stability data of South China Power Grid obtained by off-line calculation and that obtained by on-line calculation, the impacts of following factors, e.g., neglecting a certain scale of generators and loads simultaneously, neglecting the data of 220kV power network, shifting power load from 110kV side to 220kV side and neglecting Hong Kong power network etc., the on-line analysis results of South China Power Grid are analyzed, and the suggestions on rationally enlarging the on-line data acquisition scale of SCADA/EMS is put forward. By use of dynamic equivalence technique, two equivalent schemes corresponding to current data scale of South China Power Grid and the suggested development scale are proposed, and the comparative analysis on these two schemes are performed in respect of power flow distribution, short circuit currents, typical fault analysis and so on, analysis results show that the suggested scheme is more adaptive in keeping system stability characteristic.
Keywords:south China power grid  dynamic equivalence  on-line analysis  SCADA  EMS