首页 | 官方网站   微博 | 高级检索  
     

计及磁饱和的同步发电机内电势幅值测量方法
引用本文:王茂海,齐霞.计及磁饱和的同步发电机内电势幅值测量方法[J].电力系统自动化,2016,40(6):134-138.
作者姓名:王茂海  齐霞
作者单位:国家电网华北电力调控分中心, 北京市 100053,国网冀北电力有限公司经济技术研究院, 北京市 100005
基金项目:国家电网公司科技项目(5201011400M5)
摘    要:在直接测量转子位置获取同步发电机内电势相位的基础上,给出了同步发电机内电势幅值的准确直接计算方法,该方法的准确性只依赖于机端电压、机端电流、发电机功角等电气测量结果的准确性,与同步发电机参数无关。同时,基于内电势幅值和相位的准确测量,给出了能够计及磁路饱和影响的同步发电机定子与转子间互感电抗和同步电抗的计算方法,并基于正态分布参数估计理论,给出电抗计算结果的置信区间和点估计值,实际算例表明,所述方法准确可靠。

关 键 词:广域测量系统  相量测量装置  内电势  同步电抗  参数辨识
收稿时间:2015/7/15 0:00:00
修稿时间:2015/12/9 0:00:00

An Internal Voltage Measuring Method for Generators Taking Saturation into Account
WANG Maohai and QI Xia.An Internal Voltage Measuring Method for Generators Taking Saturation into Account[J].Automation of Electric Power Systems,2016,40(6):134-138.
Authors:WANG Maohai and QI Xia
Affiliation:North China Branch of National Power Dispatching & Control Center, Beijing 100053, China and State Grid Jibei Electric Economic Research Institute, Beijing 100005, China
Abstract:The angle of a synchronous generator's internal voltage can be directly calibrated against the rotor position acquired by the phasor measurement unit(PMU). However, presently, there is no direct method to calculate the amplitude of internal voltage. Based on accurate measurement of the internal voltage angle, this paper proposes a direct method to calculate internal voltage amplitude. The proposed method has nothing to do with the generator's parameters, its accuracy depends only on the measuring accuracy of the electrical measurements(including terminal voltage, terminal current and power angle). Furthermore, a method of calculating xd(d-axis synchronous reactance)and xdf(mutual reactance between field winding and stator winding)is proposed, which is capable of taking into account the influence of magnetic saturation. Based on the statistical theory of normal distribution, a robust parameter identification algorithm is proposed to give the confidence interval and point estimation of xd and xdf. Examples based on the wide area measurement system(WAMS)at North China power grid show that the proposed method is feasible and reliable.
Keywords:wide area measurement system(WAMS)  phasor measurement unit(PMU)  internal voltage  synchronous reactance  parameter identification
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号