首页 | 官方网站   微博 | 高级检索  
     

基于负荷监测系统的配电网故障测寻方法
引用本文:武鹏,徐群,沈忠旗,程浩忠.基于负荷监测系统的配电网故障测寻方法[J].电力系统自动化,2012,36(3):111-115.
作者姓名:武鹏  徐群  沈忠旗  程浩忠
作者单位:1.上海市电力公司松江供电公司,上海市 201600; 2.上海交通大学电子信息与电气工程学院,上海市 200240
摘    要:根据负荷监测系统实时采集的配电网杆上变压器(简称杆变)低压侧三相电压数值变化情况,对配电网中的故障部分进行分析定位。在发生单相断线故障时,通过对比分析配电馈线部分位置上的配电变压器低压侧三相电压数值判定单相断线发生的地点,进一步结合配电变压器绕组接线模式确定断线线路的相位信息。对于杆变内部故障引起的馈线开关跳闸、重合成功,通过该杆变的低压侧电压数值的有无判定故障原因和故障地点。对发生在松江电网实际故障的处理过程可以看出所提出方法在配电网故障处理中的正确性和有效性。

关 键 词:负荷监测系统  配电网  单相断线故障  杆变内部故障  快速寻址
收稿时间:2011/5/28 0:00:00
修稿时间:1/9/2012 7:45:00 AM

Application of Load Monitoring System in Disposing Fault of Distribution Network
WU Peng,XU Qun,SHEN Zhongqi,CHENG Haozhong.Application of Load Monitoring System in Disposing Fault of Distribution Network[J].Automation of Electric Power Systems,2012,36(3):111-115.
Authors:WU Peng  XU Qun  SHEN Zhongqi  CHENG Haozhong
Affiliation:1.Songjiang Power Supply Company of SMEPC,Shanghai 201600,China; 2.School of Electronic Information and Electrical Engineering,Shanghai Jiaotong University,Shanghai 200240,China)
Abstract:According to the variation of the three-phase voltage data gathered in real time from the load monitoring system,the location of some faults in the distribution network can be analyzed and judged.When single-phase disconnection fault occurs,the address of disconnection can also be judged according to the voltage waves of two adjacent load monitoring devices.Also the disconnection phase can be ascertained by combining the connection mode of the distribution transformer.For the case where the transformer inner fault happens and the breaker in substation trips then auto-reclose acts successfully,the reason and location of the fault transformer can be judged according to the presence or absence of voltage data from the load monitoring device.It can be seen from the process of handling the actual fault in the distribution network of Songjiang district,the validity and effectiveness of the load monitoring system in coping with the single-phase disconnection fault is obvious.
Keywords:load monitoring system  distribution network  single-phase disconnection fault  transformer inner fault  quick address seeking
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23