首页 | 官方网站   微博 | 高级检索  
     

35kV单进线变电站雷电侵入过电压的研究
引用本文:王晓阳,李随林,舒晓丽,郭建民,葛小燕,杨大卫.35kV单进线变电站雷电侵入过电压的研究[J].西北电力技术,2005,33(3):1-5,32.
作者姓名:王晓阳  李随林  舒晓丽  郭建民  葛小燕  杨大卫
作者单位:[1]安康供电局,陕西安康725000 [2]西北电力试验研究院,陕西西安710054
摘    要:对35kV单进线的终端变电站,当雷电绕击到进线段导线而侵入变电站时,现有的避雷器保护方式不能满足要求。采用EMTP程序计算得出,应再增加一组避雷器,并在实际中得到应用。

关 键 词:雷电侵入波  末端变电站  过电压计算  措施

Study on Lightning Invasion Over-voltage in 35kV Substation with Single Incoming Line
WANG Xiaoyang,LI Suilin,SHU Xiaoli et al.Study on Lightning Invasion Over-voltage in 35kV Substation with Single Incoming Line[J].Northwest China Electric Power,2005,33(3):1-5,32.
Authors:WANG Xiaoyang  LI Suilin  SHU Xiaoli
Abstract:In the light of 35kV terminal substation with single incoming line, the current lightning protection mode can not satisfy the requirement when lightning make detour struck on the line and invade in substation. The calculation by using EMTP program shows that it is necessary to add a group of lighting arrestor. And this has been applied in substatioa
Keywords:invasion wave terminal substation over-voltage calculation measure  
本文献已被 CNKI 维普 等数据库收录!