首页 | 官方网站   微博 | 高级检索  
     

不同连接方式下直流场回路支柱绝缘子抗震性能研究
引用本文:姜斌,谢强,何畅,卓然,胡蓉,孙帮新.不同连接方式下直流场回路支柱绝缘子抗震性能研究[J].高压电器,2019,55(6):124-130.
作者姓名:姜斌  谢强  何畅  卓然  胡蓉  孙帮新
作者单位:同济大学土木工程学院,上海,200092;南方电网科学研究院,广州,510080;中国南方电网超高压输电公司,广州,510620
基金项目:霍英东教育基金;南方电网科技项目
摘    要:为对比全硬管母连接和分段管母组合六分裂导线连接两种连接方式对直流场回路抗震性能的影响,以某换流站直流场±400 kV回路为研究对象,建立了不同连接条件下该回路的精细化有限元模型,获得了回路支柱绝缘子的地震响应。对不同条件下回路中支柱绝缘子的地震响应进行了对比分析,发现绝缘子的位置和回路的连接方式对绝缘子地震响应有较大影响。进一步得到如下结论:该回路在地震作用下易发生整体扭转,回路两端绝缘子地震响应较中间绝缘子大;全硬管母连接方式下回路整体性好,地震响应可以较好的均分给各个支柱绝缘子,分段管母加六分裂导线连接的回路整体性略差,平行弱轴的回路部分中设备的地震响应有明显增大;非直线布置耦联体系中平行弱轴的回路部分中设备的地震响应较大。

关 键 词:支柱绝缘子  硬管母  六分裂导线  抗震性能  数值仿真

Seismic Performance of Post Insulators in the Loop of DC Field Under Different Connection Modes
JIANG Bin,XIE Qiang,HE Chang,ZHUO Ran,HU Rong,SUN Bangxin.Seismic Performance of Post Insulators in the Loop of DC Field Under Different Connection Modes[J].High Voltage Apparatus,2019,55(6):124-130.
Authors:JIANG Bin  XIE Qiang  HE Chang  ZHUO Ran  HU Rong  SUN Bangxin
Affiliation:(College of Civil Engineering,Tongji University,Shanghai 200092,China;Electric Power Research Institute,CSG,Guangzhou 510080,China;CSG EHV Power Transmission Company,Guangzhou 510620,China)
Abstract:To compare the influences of two connection modes on the seismic performance of the loop in DC field,a±400 kV loop in a DC field in a converter substation is taken as the objective to establish a refined finite element model for analyzing its seismic performance.The seismic responses of the loop under different input ground motions are obtained.It is found that the location of insulator and the connection mode of loop have great influences on the seismic response of the insulators.It is concluded that the loop has an overall torsional effect under seismic action,and the dynamic responses of the insulators at both ends are larger.The integrity of the loop connecting with rigid tubular bus is better.The seismic response of the loop in rigid connection mode is more evenly distributed to each insulator than that inflexible connection mode.The integrity of the loop connecting with rigid tubular bus and 6-bundle conductors is poor.The seismic response of the equipment in the loop parallel to the weak axis increases obviously.And for nonlinear arrangement,the seismic response of the equipment in the loop parallel to the weak axis is greater.
Keywords:post insulator  rigid tubular bus  6-bundle conductor  seismic performance  numerical simulation
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号