Heat transfer and pressure drop during HFC refrigerant saturated vapour condensation inside a brazed plate heat exchanger
Authors:Giovanni A Longo
Affiliation:1. Department of Mechanical Engineering, Science and Research Branch, Islamic Azad University, Arak, Iran;2. Department of Chemical Engineering, Amirkabir University of Technology (Tehran Polytechnic), Tehran 15875-4413, Iran;3. Department of Mechanical Engineering, South Tehran Branch, Islamic Azad University, Tehran, Iran;1. Energy Engineering Department, School of Engineering, University of Management & Technology, C-II Johar Town Lahore, Pakistan;2. Energy System Engineering, Korea University of Science and Technology, 217 Gajeong-ro, Yuseong-gu, Daejeon, Republic of Korea;3. Energy Efficiency Research Division, Korea Institute of Energy Research, 152 Gajeong-ro, Yuseong-gu, Daejeon, Republic of Korea;4. Department of Mechanical Engineering, University of Engineering & Technology, Lahore, G.T Rd, Lahore 54890, Pakistan
Abstract:This paper presents the heat transfer coefficients and the pressure drop measured during HFC refrigerants 236fa, 134a and 410A saturated vapour condensation inside a brazed plate heat exchanger: the effects of saturation temperature (pressure), refrigerant mass flux and fluid properties are investigated. The heat transfer coefficients show weak sensitivity to saturation temperature (pressure) and great sensitivity to refrigerant mass flux and fluid properties. A transition point between gravity controlled and forced convection condensation has been found for a refrigerant mass flux around 20 kg/m2s that corresponds to an equivalent Reynolds number around 1600–1700. At low refrigerant mass flux (Gr < 20 kg/m2s) the heat transfer coefficients are not dependent on mass flux and are well predicted by the Nusselt 20] analysis for vertical surface: the condensation process is gravity controlled. For higher refrigerant mass flux (Gr > 20 kg/m2s) the heat transfer coefficients depend on mass flux and are well predicted by Akers et al. 21] equation: forced convection condensation occurs. In the forced convection condensation region the heat transfer coefficients show a 25–30% increase for a doubling of the refrigerant mass flux.The frictional pressure drop shows a linear dependence on the kinetic energy per unit volume of the refrigerant flow and therefore a quadratic dependence on mass flux.HFC-410A shows heat transfer coefficients similar to HFC-134a and 10% higher than HFC-236fa together with frictional pressure drops 40-50% lower than HFC-134a and 50–60% lower than HFC-236fa.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号