首页 | 官方网站   微博 | 高级检索  
     


Reasons for drop in shell-and-tube condenser performance when replacing R22 with zeotropic mixtures. Part 2: investigation of mass transfer resistance effects
Authors:Tord Karlsson  Lennart Vamling  
Affiliation:Heat and Power Technology, Department of Chemical Engineering and Environmental Science, Chalmers University of Technology, SE-412 96, Gothenburg, Sweden
Abstract:Detailed calculations of condensation outside a column of horizontal smooth tubes have been carried out in order to investigate the influence of mass transfer resistance for a zeotropic refrigerant mixture. Diffusive transport is calculated locally in both phases. Calculation results show that mass transfer resistance in the gas phase reduces heat transfer by 10–20% for a binary mixture with a glide similar to that of R407C.The decrease in heat transfer due to poor mixing in the condensate is from 15 to 65% for the conditions investigated; the lower the duty, the greater the decrease. Results show that if assuming mixing in the condensate by diffusion only, the degrees of mixing and the duty dependency are similar to results in earlier work where calculations were matched to experimental data. Diffusion is likely to be the dominant mixing mechanism in the condensate, and the mixing is poor under certain conditions, which might explain the drop in condenser performance for some heat pump applications.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23