首页 | 官方网站   微博 | 高级检索  
     


An aquifer thermal storage system in a Belgian hospital: Long-term experimental evaluation of energy and cost savings
Authors:D Vanhoudt  J DesmedtJ Van Bael  N RobeynH Hoes
Affiliation:a Flemish Institute for Technological Research “VITO”, Boeretang 200, 2400 Mol, Belgium
b Terra Energy, Industriezone Vlasmeer 5/000, 2400 Mol, Belgium
Abstract:Over a three years period, an aquifer thermal energy storage system was monitored in combination with a heat pump for heating and cooling of the ventilation air in a Belgian hospital. The installation was one of the first and largest ground source heat pump systems in Belgium. Groundwater flows and temperatures were monitored as well as the energy flows of the heat pumps and the energy demand of the building. The resulting energy balance of the building showed that the primary energy consumption of the heat pump system is 71% lower in comparison with a reference installation based on common gas-fired boilers and water cooling machines. This corresponds to a CO2-reduction of 1280 ton over the whole measuring period. The overall seasonal performance factor (SPF) for heating was 5.9 while the ATES system delivered cooling at an efficiency factor of 26.1. Furthermore, the economic analysis showed an annual cost reduction of k€ 54 as compared to the reference installation, resulting in a simple payback time of 8.4 years, excluding subsidies.
Keywords:Hospital  Aquifer thermal energy storage  ATES  Monitoring  Geothermal energy  Ground source heat pump  Primary energy savings
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号