Abstract: | An experimental system investigating condensation heat transfer of wet flue gas was set up, and the heat transfer performance of vapor‐gas mixture with vapor condensation was discussed. The experimental results of laminar flow in a plastic longitudinal spiral plate heat exchanger were obtained and are in good agreement with the modified classical film model. It is shown that the plastic air preheater can avoid acid corrosion in the low‐temperature field for the boiler using fuel containing sulfur and recover latent heat of the water vapor of the wet flue gas. Also some SO2 was scrubbed during the vapor condensing process in the heat exchanger. © 2001 Scripta Technica, Heat Trans Asian Res, 30(7): 571–580, 2001 |