首页 | 官方网站   微博 | 高级检索  
     

有源配电网的安全距离与安全分析方法
引用本文:肖峻,林启思,左磊,周欢.有源配电网的安全距离与安全分析方法[J].电力系统自动化,2018,42(17):76-86.
作者姓名:肖峻  林启思  左磊  周欢
作者单位:智能电网教育部重点实验室(天津大学)
基金项目:国家重点研发计划资助项目(2016YFB0900100);国家自然科学基金资助项目(51477112)
摘    要:提出了有源配电网的安全距离与安全分析方法。首先,提出了状态距离的概念,并建立了按方向和长短分类的有源配电网安全距离概念族。其次,提出了有源配电网中各类安全距离的计算方法,考虑了安全距离不存在或无穷大的情况,且能求解正、反向潮流边界的安全距离。再次,提出了基于状态安全距离排序的安全分析方法,得到最危险和最安全的方向及代价最小的安全控制方案;分析结果还包括越界边界、越界点、位移以及垂向轴向越界方向、正反向越界模式等丰富信息。最后,通过算例验证了所提方法。文中发展完善了配电网安全距离这一重要概念,越界分析方法也丰富了现有安全分析内容。

关 键 词:有源配电网  安全距离  安全分析  状态距离  反向潮流边界  安全控制  越界分析
收稿时间:2018/2/2 0:00:00
修稿时间:2018/8/9 0:00:00

Security Distance and Security Analysis Method for Active Distribution Network
XIAO Jun,LIN Qisi,ZUO Lei and ZHOU Huan.Security Distance and Security Analysis Method for Active Distribution Network[J].Automation of Electric Power Systems,2018,42(17):76-86.
Authors:XIAO Jun  LIN Qisi  ZUO Lei and ZHOU Huan
Affiliation:Key Laboratory of Smart Grid of Ministry of Education(Tianjin University), Tianjin 300072, China,Key Laboratory of Smart Grid of Ministry of Education(Tianjin University), Tianjin 300072, China,Key Laboratory of Smart Grid of Ministry of Education(Tianjin University), Tianjin 300072, China and Key Laboratory of Smart Grid of Ministry of Education(Tianjin University), Tianjin 300072, China
Abstract:This paper proposes the security distance and a security analysis method for active distribution network. Firstly, the concept of state distance is proposed and the security distance concept clan for active distribution network is established according to directions and length. Secondly, security distance calculation methods are discussed considering the inexistence and infinity of security distance for active distribution network. These methods can solve the security distance to positive and negative power flow boundaries. Then, a security analysis method based on the state security distance order is proposed, which finds the most dangerous and safest directions and security control plans with minimum cost. Analysis results also includes crossing boundaries, crossing points, displacement, vertical and axial crossing boundary directions, positive and negative crossing boundaries patterns and other abundant information. Lastly, proposed methods are verified by test cases, which help to develop and complete the concept of security distance for distribution system. The crossing boundaries analysis method also enriches the security analysis content in existence.
Keywords:active distribution network  security distance  security analysis  state distance  negative power flow boundaries  security control  crossing boundaries analysis
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息
点击此处可从《电力系统自动化》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23