A study on an optimal approach temperature control strategy of condensing water temperature for energy saving |
| |
Authors: | Chia-Wei LiuYew-Khoy Chuah |
| |
Affiliation: | Graduate Institute of Mechanical and Electrical Engineering, National Taipei University of Technology, Taipei, Taiwan, ROC |
| |
Abstract: | An optimal approach temperature (OAT) control strategy is proposed for resetting the condensing water temperature hourly, so to maximize the performance of the combined water chiller and cooling tower system. A system performance factor is introduced for evaluation of the system performance. A regression function is presented for the calculation of an optimal condensing water temperature at each hour of air-conditioning operation. The parameters in the regression function include the ambient wet bulb temperature, the chiller load ratio at the hour, and a dimensionless relative efficiency of chiller and cooling tower. The regression function has an R2 close to 1 compared to the computed results. When applied to two cities in Taiwan, the OAT control strategy has a potential to save energy more than 4% on an annual basis. The OAT control strategy is most advantageous when applied to regions with large seasonal variation of wet bulb temperature. |
| |
Keywords: | Cooling tower Energy saving Temperature Wet bulb |