首页 | 官方网站   微博 | 高级检索  
     


Energetic and exergetic performance analysis of Bethe-Zeldovich-Thompson (BZT) fluids in geothermal heat pumps
Authors:Oznur OzcanOnder Ozgener
Affiliation:a Graduate School of Natural and Applied Sciences, Solar Energy Science Branch, Ege University, TR-35100, Bornova, Izmir, Turkey
b Solar Energy Institute, Ege University, TR-35100, Bornova, Izmir, Turkey
Abstract:This study highlights theoretical energetic and exergetic performance evaluation results of Bethe-Zeldovich-Thompson (BZT) fluids in geothermal heat pumps. In this study, hexafluoroethane (R116), octafluoropropane (R218), and octafluorocyclobutane (RC318) were selected as possible alternative replacements to the traditional refrigerants in geothermal heat pumps. According to the calculations, coefficient of performance of 101 kW geothermal heat pumps (COPHP) changes with range between 3.84, 3.08, and 2.92 for octafluorocyclobutane (RC318), hexafluoroethane (R116), and octafluoropropane (R218), respectively. Moreover, R116 shows the maximum exergy efficiency 68% among the selected BZT fluids.
Keywords:COP  Energy  Exergy  Heat pump  Refrigerant
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号