首页 | 官方网站   微博 | 高级检索  
     


Experimental studies on air-cooled NH3-H2O based modified gax absorption cooling system
Authors:CP Jawahar R Saravanan
Affiliation:R&AC Laboratory, Dept. of Mechanical Engineering, College of Engineering, Guindy, Anna University, Chennai 600 025, India
Abstract:An experimental investigation on the performance of an air-cooled modified generator absorber heat exchange (GAX) absorption cooling system has been carried out and presented in this paper. The conventional system is modified by incorporating high pressure GAX, low pressure GAX, a solution cooler and an additional solution heat exchanger to reduce the heat input to the system. The system is designed for a cooling capacity of 10.5 kW using ammonia-water (NH3-H2O) as the working fluid. The performance of the system in terms of the circulation ratio, internal heat recovery and coefficient of performance (COP) has been obtained. The system is capable of producing a low evaporator temperature of −5 °C, at a sink temperature of 35 °C, under no load conditions. The results indicate that at a generator and evaporator temperature of 120 °C and 2 °C respectively, the system delivers a maximum cooling capacity of about 9.5 kW with a fuel and total COP of 0.61 and 0.57 respectively.
Keywords:Absorption  Air-cooled  Ammonia-water  COP  Heat recovery
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23