500 kV绝缘横担杆塔电气性能分析
引用本文:张志劲,杨超,蒋兴良,胡建林,胡琴.500 kV绝缘横担杆塔电气性能分析[J].中国电力,2013,46(9):56-60.
作者姓名:张志劲  杨超  蒋兴良  胡建林  胡琴
作者单位:重庆大学 输配电装备及系统安全与新技术国家重点实验室,重庆 400044
基金项目:国家重点基础研究发展计划资助项目(973项目)
摘    要:随着国家加大超/特高压输电线路的建设力度,对输电线路杆塔的绝缘性能要求也越来越高。结合绝缘杆塔的国内外研究应用现状,提出绝缘杆塔的结构型式;以绝缘横担杆塔为例,参考500 kV单回路酒杯型杆塔,计算了绝缘横担杆塔和普通铁塔的绝缘水平,并在此基础上分析了两者在电气性能上的差异;从减少绝缘子片数和缩短横担长度2个方面分析了其对绝缘杆塔电气性能的影响。研究结果表明:绝缘横担杆塔在工频电压、操作过电压以及雷电过电压下的绝缘裕度都要高于普通杆塔;要实现绝缘杆塔安全性和经济性的统一,可以在减少绝缘子片数的同时适当缩短绝缘横担长度。

关 键 词:绝缘杆塔  绝缘配置  绝缘子片数  绝缘横担  绝缘裕度  
收稿时间:2013-03-02

Analysis on the Electric Performance of 500 kV Tower with Insulated Cross-Arm
ZHANG Zhi-jin , YANG Chao , JIANG Xing-liang , HU Jian-lin , HU Qin.Analysis on the Electric Performance of 500 kV Tower with Insulated Cross-Arm[J].Electric Power,2013,46(9):56-60.
Authors:ZHANG Zhi-jin  YANG Chao  JIANG Xing-liang  HU Jian-lin  HU Qin
Affiliation:State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University,Chongqing 400044, China
Abstract:The accelerated construction of UHV transmission lines by the state brings about, higher insulation performance requirements for the UHV transmission line towers. Based on an investigation of the research and application status of insulation towers, the paper proposes the structure pattern of insulation towers. By taking the insulated cross-arm tower as an example and with a reference to the 500 kV single circuit cup-type tower, the insulation level of the insulated cross-arm towers and the ordinary towers are calculated and the difference of their electrical performances are compared. The impacts of two factors, including reducing the number of insulators and shortening the length of insulated cross-arm, are analyzed on the electric performance of insulation towers. The results show that the towers with insulated cross-arms are superior over the common towers in terms of insulating margin under frequency voltage, switching overvoltage and lightning overvoltage. It can be concluded that number of insulators and the length of the insulated cross-arms may be reduced concurrently to achieve the unification of the safety and economy of insulation towers.
Keywords:insulation tower  insulation configuration  the number of insulators  insulated cross-arm  insulation margin