特高压长串绝缘子对风偏计算的影响研究
引用本文:闵绚,文志科,吴向东,邵瑰玮,季坤,蔡焕青.特高压长串绝缘子对风偏计算的影响研究[J].中国电力,2014,47(1):28-34.
作者姓名:闵绚  文志科  吴向东  邵瑰玮  季坤  蔡焕青
作者单位:1. 中国电力科学研究院,湖北 武汉 430074;
2. 国网湖北省电力公司,湖北 武汉 430077;
3. 国网安徽省电力公司,安徽 合肥 230061
摘    要:输电线路的风偏角计算所采用的都是刚体静力学模型。为了简化计算,该模型将绝缘子串和导线假设为刚体,风吹时绝缘子串不发生任何弯曲或变形。特高压线路的绝缘子串较长,风吹时其链式弯曲程度较低电压等级输电线路的绝缘子串要大,需要研究其对线路风偏角的影响。通过数值仿真计算和风偏模拟验证试验得到的结果表明,特高压线路采用棒型绝缘子可不考虑绝缘子链式弯曲的影响,但采用盘形绝缘子串,当绝缘子串两端相邻的导线悬挂点高于其自身时则需考虑,即按现有方法计算出绝缘子串的水平位移,并加上由链式弯曲引起的偏差值,否则将来可能存在特高压线路塔头部位风偏故障的隐患。

关 键 词:绝缘子串  链式结构  刚体静力学模型  风偏角  风荷载  
收稿时间:2013-11-08

Research on the Windage Yaw Calculation of UHV Long Insulator String
MIN Xuan,WEN Zhi-ke,WU Xiang-dong,SHAO Gui-wei,JI Kun,CAI Huan-qing.Research on the Windage Yaw Calculation of UHV Long Insulator String[J].Electric Power,2014,47(1):28-34.
Authors:MIN Xuan  WEN Zhi-ke  WU Xiang-dong  SHAO Gui-wei  JI Kun  CAI Huan-qing
Affiliation:1. China Electric Power Research Institute, Wuhan 430074, China;
2. State Grid Hubei Electric Power Company, Wuhan 430077, China;
3. State Grid Anhui Electric Power Company, Hefei 230061, China
Abstract:Calculation of windage yaw angle of transmission lines is usually made by rigid body statics model. In order to simplify the calculation process, it is supposed in this model that the insulator string and conductor are rigid body, and no bending or deformation occur for the insulator string when wind blows. For the UHV transmission line, however, the chain structure bending extent of the UHV insulator string is higher than that of lower voltage transmission lines when wind blows because of its longer insulator string. It is therefore imperative to study the effects of long insulator string on the windage yaw angle of transmission lines. Numerical simulation and simulation verification test of windage yaw shows that when rod insulator string is used for UHV transmission lines, the effects of the chain structure bending can be ignored; but for the disk insulator string, when the adjacent conductor hanging points are higher than the insulator string itself, the effects shall be taken into consideration, i.e., the horizontal displacement of insulator string calculated by the existing method shall be added by the deviation value caused by chain structure bend of insulator string, otherwise the windage yaw fault may occur for the UHV tower head
Keywords:insulator string  chain structure bend  rigid body statics model  windage yaw angle  wind load  