Recommended Concentration Limits of Typical Indoor Air Contaminants
Authors:LV Chao  JIANG Yun-tao  ZHAO Jia-ning
Abstract:From the view of both objective and subjective factors.the indoor air quality(IAQ)evaluation was considered.Carbon dioxide (CO2) and formaldehyde (HCHO) were selected as the typical contaminants of indoor air,and the evaluation method of logarithmic index was adopted as the evaluation means of IAQ.Then the recommended limits (RL) of typical contaminants CO2 and HCHO were given through analysis and calcula-tion.The limits of CO2 and HCHO in Indoor Air Quahty Standard of China or other existing standards probably correspond to the level of PD=25(%).The result shows that the existing standards fail to meet the require-ment of the definition of"acceptable indoor air quality",that is to say,less than 20% of the people express dis-satisfaction.When PD=20%,RL of CO2 and HCHO are 728×10-6 and 0.068×10-6 respectively,which are stricter than the limits in the existing standards.The method proposed in this paper is applicable to 13.1%≤PD≤86.7%.
Keywords:indoor air quality(IAQ)  typical contaminants  recommended limits(RL)  evaluation method of logarithmic index  percentage of dissatisfaction(PD)