首页 | 官方网站   微博 | 高级检索  
     

110kV线路型避雷器
引用本文:贺建国,李凡,施围.110kV线路型避雷器[J].电瓷避雷器,2000(4):37-41.
作者姓名:贺建国  李凡  施围
作者单位:西安交通大学,陕西,西安,710049
摘    要:根据具体的线路杆塔 ,采用有串联间隙金属氧化物避雷器对 1 1 0 k V线路的耐雷水平进行了计算分析 ;具体比较了安装线路避雷器和未装避雷器时雷击杆塔以及雷击线路的耐雷水平 ;分析了雷电流的模型、接地电阻、避雷器最大耐受冲击电流、避雷器热容量等对线路耐雷水平影响

关 键 词:金属氧化物避雷器  耐雷水平  接地电阻  冲击电流
修稿时间::

The 110kV Transmission Line Arrestor
HE Jian-guo,LI Fan,SHI Wei.The 110kV Transmission Line Arrestor[J].Insulators and Surge Arresters,2000(4):37-41.
Authors:HE Jian-guo  LI Fan  SHI Wei
Abstract:Calculation and evaluation of ligtning withstand level of 110kV overhead transmission line with poles of given structure using gapped MOA is presented.The lightning withstand level of transmission line with and without arrestor are analyzed for cased of lightning strick onto line conductor and line pole,such as the model of lightning current, grounding resistance, maximum withstand surge and the energe absorb capability of arrestor.
Keywords:MOA  lightning withstand level  grounding resistance  the current impulse
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司    京ICP备09084417号-23

京公网安备 11010802026262号