高压直流输电系统接地极不平衡保护改进措施研究
引用本文:曾祥君,张玺,阳韬,邓曙光.高压直流输电系统接地极不平衡保护改进措施研究[J].电力系统保护与控制,2014,42(24):132-137.
作者姓名:曾祥君  张玺  阳韬  邓曙光
作者单位:湖南城市学院,湖南 益阳 413099;长沙理工大学智能电网运行与控制湖南省重点实验室,湖南 长沙 410114;长沙理工大学智能电网运行与控制湖南省重点实验室,湖南 长沙 410114;长沙理工大学智能电网运行与控制湖南省重点实验室,湖南 长沙 410114;湖南城市学院,湖南 益阳 413099
基金项目:国家自然科学基金(61233008,51207013);湖南省科技重大专项(2012FJ1003);湖南省高校产业化培育项目(12CY007)
摘    要:接地极是高压直流输电系统中最重要的组成部分之一。为了提高接地极保护可靠性,根据接地极线路参数及运行特性,提出了一种基于纵联差动保护原理的接地极不平衡保护方法。该方法将互感器装设在接地极引线的近站端和极址端,给出了纵差保护方案和保护判据,优化了保护动作策略,分析了保护动作特性。仿真结果表明,提出的接地极不平衡保护能准确辨识故障类型,准确动作隔离故障,有效降低直流系统停运概率。

关 键 词:接地极  不平衡保护  电子式互感器  纵差保护
收稿时间:2014/3/10 0:00:00
修稿时间:8/6/2014 12:00:00 AM

Improvement measures of electrodes line unbalance protection for HVDC system
ZENG Xiang-jun,ZHANG Xi,YANG Tao and DENG Shu-guang.Improvement measures of electrodes line unbalance protection for HVDC system[J].Power System Protection and Control,2014,42(24):132-137.
Authors:ZENG Xiang-jun  ZHANG Xi  YANG Tao and DENG Shu-guang
Affiliation:Hunan City University, Yiyang 413099, China; Hunan Province Key Laboratory of Smart Grids Operation and Control, Changsha University of Science and Technology, Changsha 410114, China;Hunan Province Key Laboratory of Smart Grids Operation and Control, Changsha University of Science and Technology, Changsha 410114, China;Hunan Province Key Laboratory of Smart Grids Operation and Control, Changsha University of Science and Technology, Changsha 410114, China;Hunan City University, Yiyang 413099, China
Abstract:Grounding electrode is the most important part of HVDC systems. In order to improve the reliability of grounding electrodes line protection, a new unbalance current protection based on the longitudinal differential protection principle is proposed. The protection transformers are installed in the head and end of the grounding electrode line, the longitudinal differential protection scheme and criterion are presented, the original action strategy is optimized and the protection action characteristics are analyzed. The simulation results show that the unbalance protection is effective, which could accurately distinguish the fault types and act to isolate faults, and reduce the probability of HVDC shutdown.
Keywords:grounding electrode  unbalance protection  ECT  longitudinal differential protection