500kV变电站雷击保护的建模分析
引用本文:匡洪海,肖伸平.500kV变电站雷击保护的建模分析[J].高压电器,2008,44(5).
作者姓名:匡洪海  肖伸平
作者单位:湖南工业大学,湖南,株洲,412000
摘    要:笔者利用国际先进的图形化电磁暂态计算程序ATPDraw3.5进行500kV变电站雷击过电压的建模研究。在研究时将变电站和进线段结合起来,考虑雷击点的近雷区和远雷区、雷击杆塔绝缘子串冲击伏秒特性、线路上的感应过电压、工频过电压和进线段杆塔冲击接地电阻等因素的影响,从而对雷电侵入波系统进行建模分析。这为防护雷电过电压、保护电气设备提供了有价值的参考依据,为高压变电所雷击保护研究分析提供了有效的方法。

关 键 词:ATPDraw3.5  雷击  过电压  建模

Modeling and Analysis of Lightning Protection for 500 kV Substation
KUANG Hong-hai,XIAO Shen-ping.Modeling and Analysis of Lightning Protection for 500 kV Substation[J].High Voltage Apparatus,2008,44(5).
Authors:KUANG Hong-hai  XIAO Shen-ping
Abstract:This paper investigates modeling of lightning overvoltage on 500 kV substation by making use of the advanced software ATPDraw3.5,in which substation and incoming line are banded together as an object.The ATP modeling process of lightning surge system is analyzed considering such factors as near lightning strike area,far lightning strike area,impulse volt-second characteristic of lightning tower insulator string,induced overvoltage and power frequency overvoltage of the line, and tower impulse grounding impedance of incoming line,etc.The result may facilitate the prevention of lightning overvohage on high-voh substation.
Keywords:ATPDraw3  5