Impact Analyses of Wind Farm on Performances ofTransmission Line Relay Protection
Authors:Jin WANG  Baohui ZHANG
Affiliation:(School of Electrical Engineering,Xi’an Jiaotong University,Xi’an 710049,China)
Abstract:A simulation system for power grid with concentrated large-scale wind farm integration is established based on the electro-magnetic transient model of wind turbine equipped with doubly-fed induction generator (DFIG),which is built by real-time digital simulator (RTDS).Using the hardware communication interface of RTDS,a closed-loop testing experiment is accomplished to study the impacts of large-scale wind farms on the existing relay protection devices for wind farm outgoing transmission line.This paper points out problems existing in current relay protection devices as follows:fault phase selector can select unwanted phase due to the changes of fault features caused by special network connection of wind farms;blocking condition for distance protections needs to be re-examined due to the weak power-feed characteristics of wind farms;and power frequency parameter based relay protection devices cannot accurately operate due to the special transient voltage and current characteristics of wind farms during fault period.Results lay the foundation for improving the performances of the existing relay protection device and developing new principle relay protection.
Keywords:wind farm  transmission line  relay protection  doubly-fed induction generator (DFIG)  real-time digital simulator (RTDS)