A self‐commutated back‐to‐back system and its performance under a single line‐to‐ground fault condition
Authors:Makoto Hagiwara  Hirofumi Akagi  Hideaki Fujita
Abstract:This paper deals with a self‐commutated BTB (Back‐To‐Back) system for the purpose of power flow control and/or frequency change in transmission systems. Each BTB unit consists of two sets of 16 three‐phase voltage‐source converters, and their AC terminals are connected in series to each other via 16 three‐phase transformers. Hence, the BTB unit uses totally 192 switching devices capable of achieving gate commutation. This results in a great reduction of voltage and current harmonics without performing PWM control. Simulation results verify the validity of the proposed system configuration and control scheme not only under a normal operating condition but also under a single line‐to‐ground fault condition. © 2003 Wiley Periodicals, Inc. Electr Eng Jpn, 143(3): 68–78, 2003; Published online in Wiley InterScience ( www.interscience.wiley.com ). DOI 10.1002/eej.10124
Keywords:BTB (Back‐To‐Back) system  multi converter  power flow control  single line‐to‐ground fault condition  unit capacitance constant